ELECTRONIC CIRCULATOR FOR SOLAR THERMAL SYSTEMS - Art. S167
FI.S167.EN.C - 03/2023
Icma SpA - Via Garavaglia, 4 - 20012 Cuggiono (MI) ITALY Tel: +39 02 97249134 - +39 02 97249135 - www.icmaspa.it - [email protected]
Icma SpA - Via Garavaglia, 4 - 20012 Cuggiono (MI) ITALY Tel: +39 02 97249134 - +39 02 97249135 - www.icmaspa.it - [email protected]
22
23
14. TECHNICAL PARAMETERS AND INSTALLATION DIMENSIONS
14.1 Technical data
Supply Voltage
220~240V, 50/60Hz
Motor Protection
Pump does not need external protection
Protection Level
IP44
Insulation Class
H
Relative Humidity (RH)
Max95%
System Load Bearing
1.0 MPa
Suction Inlet Pressure
Liquid Temperature
Minimum Inlet Pressure
≤+75°C
0.005 Mpa
≤+90°C
0.028 Mpa
≤+110°C
0.100 MPa
EMC Standard
EN61000-6-1 and EN61000-6-3
Sound Pressure level
The sound pressure level of pump is lower than 42dB(A)
Ambient Temperature
0~+70°C
Temperature Grade
TF110
Surface Temperature
Maximum surface temperature should not 125°C
Liquid Temperature
+2~+110°C
To prevent the control box and stator from appearing condensate water, the temperature of pump conveying
liquid must be always higher than the ambient temperature
Ambient Temperature(°C)
Liquid Temperature
Min.(°C)
Max.(°C)
0
2
110
10
10
110
20
20
110
30
30
110
35
35
90
40
40
70