ELECTRONIC CIRCULATOR FOR SOLAR THERMAL SYSTEMS - Art. S167

FI.S167.EN.C  -  03/2023

Icma SpA - Via Garavaglia, 4 - 20012 Cuggiono (MI) ITALY Tel: +39 02 97249134 - +39 02 97249135 - www.icmaspa.it - [email protected]

16

PWM feedback signal can provide operation status of the pump, such as power loss or all kinds of alarm/warning 
modes.
PWM feedback signal will feed back exclusive alarming information. If the power voltage detects under-voltage signal 
values, its output signal will be set to 75%. Provided sundries settlement exists in the hydraulic system and causes 
rotor being blocked, the duty cycle of output signal is set to 90%, the alarm will be given higher priority.

The signal can be used to measure power consumption of the pump. The pump signal can be used to detect the 
actual operating point of the system rather than measuring by the current controlled by the system. The signal is also 
applicable to comparing velocity setting value and feedback.

8.4 PWM Feedback Signal

8.5 How to use the signals

PWM Output Signal 

(%)

Pump Status

Description

95

Standby (stop)

The pump stops

90

Alarm stops, malfunctions (pump 
blocked)

The pump does not work and will restarts only 
after trouble is addressed

85

Alarm stops, electrical 
malfunction/trouble

The pump does not work and will restarts only 
after trouble is addressed

75

Warning

The pump runs, trouble has been detected under 
this situation but it is not critical, and the pump 
can still work.

0-70

0-70W (slope 1 W/% PWM)

Содержание S167

Страница 1: ...TOR FOR SOLAR THERMAL SYSTEMS Art S167 FI S167 EN C 03 2023 Icma SpA Via Garavaglia 4 20012 Cuggiono MI ITALY Tel 39 02 97249134 39 02 97249135 www icmaspa it sales icmaspa it 1 INSTALLATION AND OPERA...

Страница 2: ...laying the settings of the pump 12 6 3Buttonforselectingthepumpsettings 12 7 SETTING OF THE PUMP 12 7 1 The control on the pump 13 8 PWM SIGNAL CONTROL MODE 14 8 1 Control and Signal 14 8 2 Interface...

Страница 3: ...and cause electrical faults 14 In the winter if the pump system does not operate or when the ambient temperature is below 0 C liquid in the pipeline system should be emptied to avoid causing frost cra...

Страница 4: ...pump is equipped with the control panel on the front which is convenient for the operation of users Easy installation and start up The pump has auto adaptation mode AUTO factory settings In most case...

Страница 5: ...t temperature 3 4 System Pressure The maximum is 1 0 MPa 10 bar 3 5 Protection Level IP 44 3 6 Inlet Pressure To avoid damage to the pump bearing caused by cavitation noise the following minimum press...

Страница 6: ...cmaspa it sales icmaspa it 6 4 INSTALLATION Install the pump arrows on the pump housing indicate the direction of liquid flowing through the pump body When the pump is installed on the pipeline its in...

Страница 7: ...crews that fix the pump body 3 Rotate the motor to the desired position and match the four screw holes 4 Put the four socket head cap screws back and tighten them in the cross direction order 5 Open t...

Страница 8: ...39 02 97249135 www icmaspa it sales icmaspa it 8 4 2 Thermal insulation of the pump body CAUTION NOTE Restrict the thermal losses of the pump body and pipeline Conduct thermal insulation for the pump...

Страница 9: ...CIRCULATOR FOR SOLAR THERMAL SYSTEMS Art S167 FI S167 EN C 03 2023 Icma SpA Via Garavaglia 4 20012 Cuggiono MI ITALY Tel 39 02 97249134 39 02 97249135 www icmaspa it sales icmaspa it 9 5 ELECTRICAL C...

Страница 10: ...wer supply and frequency match with the parameters marked by pump nameplate Use the pump associated plug to connect power supply If the indicator lamp on the control panel lights it indicates that the...

Страница 11: ...protection restart after 5S Gear light 1 2 flickers Locked rotor protection restart after 5S Gear light 1 3 flickers Start failure asymmetric motor parameters restart after 5S Gear light 1 4 flickers...

Страница 12: ...by the light lit of 10 locations By pressing the button once at 2 seconds interval the pump setting mode will change once A cycle is constituted of every nine presses on the button For details please...

Страница 13: ...evel performance curve represented by HD1 HD2 Section 11 Position System Type Settings of the pump Optimal settings Or other optional settings A Floor heating system AUTO HS3 B Dual pipeline heating s...

Страница 14: ...ntacting the signal cable 8 2 Interface NOTE Signal Ref is a reference earthing and it is not connected to protective earthing 1 Control Principle The pump is controlled by modulated LV PWM Pulse Widt...

Страница 15: ...m will have no PWM signal input In the area of high duty cycle PWM signal when the input signal fluctuates in the critical point there will be a delay area to prevent frequent stops and start of the p...

Страница 16: ...will be given higher priority The signal can be used to measure power consumption of the pump The pump signal can be used to detect the actual operating point of the system rather than measuring by th...

Страница 17: ...l the valves in the floor heating circuit or the radiator control valve temperature are closed it can be ensured that the heat from the boiler will be assigned Elements in the system Bypass valve Flow...

Страница 18: ...urer 3 When the bypass valve has been adjusted set the pump to the constant pressure mode For the relationship between pump settings and performance curve please see Section 11 Settings and Performanc...

Страница 19: ...f time In the Autoadaptation mode the pump is set to proportional pressure control mode BL 1 3 Proportional Pressure Curve The pump working point will move up and down on the proportional pressure cur...

Страница 20: ...vers a performance range Input power curve P1 curve belongs to each Q H curve Power curve represents the power consumption P1 of the pump in watts on the given Q H curve The following description appl...

Страница 21: ...RACTERISTICS 13 1 Description of nameplate No Explanation 1 Power Maximum mode maximum power Minimum mode minimum power 2 Current Maximum mode maximum current Minimum mode minimum current 3 Maximum pr...

Страница 22: ...it sales icmaspa it 22 13 2 Model explanation Pump model is consisted of upper Latin letters and Arabic numerals etc whose meanings are as follows Type key example GPA25 6B III 26 stands for a pump wi...

Страница 23: ...nlet Pressure 75 C 0 005 Mpa 90 C 0 028 Mpa 110 C 0 100 MPa EMC Standard EN61000 6 1 and EN61000 6 3 Sound Pressure level The sound pressure level of pump is lower than 42dB A Ambient Temperature 0 70...

Страница 24: ...R SOLAR THERMAL SYSTEMS Art S167 FI S167 EN C 03 2023 Icma SpA Via Garavaglia 4 20012 Cuggiono MI ITALY Tel 39 02 97249134 39 02 97249135 www icmaspa it sales icmaspa it 24 14 2 Installation Dimension...

Страница 25: ...1 3 flickers Motor resistance parameters do not match Return to factory maintenance Gear light 1 4 flickers Over heat protection Reducing ambient temperature Gear light 1 5 flickers Over temperature...

Отзывы: