26
We Think of Customer Satisfactio
n
9. Error Type
Display
Error type
Causes
Action
Release
Operation
Evaporator
temperature
error
When the Evaporator temperature
is 32℉ or more after 30 minutes
passed during the ice making
Check refrigerant
leakage
Check sensor and
attachment abnormality
Resupply power
after resolving
cooling problem
Stop ice
making
Evaporator
temperature
error
When the Evaporator temperature
is over 23℉ after 30 minutes
passed
Check refrigerant
leakage
Check sensor and
attachment abnormality
Resupply power
after resolving
cooling problem
Keep on ice
making
Temperature
sensor error
Displayed when temperature
sensor is open or shorted.
Check sensor and
attachment abnormality
Start operation
after sensor part
repair
Stop ice
making
High
pressure
switch error
Condenser dust, fan motor failure,
cold cycle abnormality, etc.
Remove dust,
Check Fan motor
Check for abnormal
cold cycle
Automatic return
after action
Stop
compressor,
Stop
motor after
operating 10
seconds.
High
pressure
switch error
Occurs when High pressure
switch is OPEN 3 times or more
Contact service
representative
Start operation
after action
Stop
compressor,
Stop
motor after
operating 10
seconds.
Water supply
error
When water level is not detected
by the water level sensor due to
no water supply for 120 seconds.
Water supply pressure
check
Water level sensor
check
Start operation
after action
Stop ice
making
Water level
sensor defect
At the start of ice making, when
the upper and lower limits are
not detected by the water level
sensor for 60 seconds
Replacement of Water
Level Sensor
Start operation
after action
Stop ice
making
Motor
restraint
Occurs when Evaporator inlet /
outlet temperature is -4℉ less
Poor water supply, Agitator
restraint, Ice jams due to scale
Unlock ice jams
Check water supply
line
Check motor restraint
fault
Start operation
after action.
Machine stops
after 3 repetitions
Stop ice
making
① When Error occurs, the front use button (ICE-WATER-ICE & WATER) of the door lights alternately
to the left and right. Restart after action.
② When the button is lit alternately to the left and right, open the door and press the bottom setting
button of the control buttons, Error display will appear.
Содержание ID-0160-AN
Страница 25: ...25 8 Circuit Diagram...
Страница 29: ...29 MEMO...
Страница 30: ...30 We Think of Customer Satisfaction MEMO...
Страница 31: ...31 MEMO...
Страница 32: ...3240453 20 Online Internet Service http www icetro com...