ELEVATION SERIES CIM CUBER REFRIGERATION SECTION
62
Hot Gas Valve
The Hot Gas Solenoid Valve opens to provide gas to the Evaporator during the Harvest Cycle.
Troubleshooting - Hot Gas Valve
Should the valve not open at the initiation of the Harvest Cycle (R3 LED ON), verify voltage at the
coil of the solenoid. If no voltage is present, verify Molex is properly connected at Board and
Voltage is present at Molex. If Voltage is present at coil, verify resistance through coil. If coil
shows open, replace the coil. If coil checks out, place magnetic donut on top of coil. If valve will
not open, replace Hot Gas Valve body. Should suction pressure run high, check temperature of
the inlet and outlet line of the Hot Gas Valve. Should be greater than 10 degree F. different. If
less than 10 degrees F., the Valve is leaking and should be replaced. (See also pg.44.)
Liquid Line Solenoid
The Liquid Line Solenoid opens to allow refrigerant to flow from the Receiver on Remote Sys‐
tems. It is energized by R1 along with the Remote Fan Motors. Diagnosis of Liquid Line Solenoid
is much the same as the Hot Gas Solenoid Valve (see above.)
Mixing Valve
The 220 psig. Mixing Valve (or LAC) Is used to maintain head pressure in low ambient .
Troubleshooting - Mixing Valve
In lower ambients, the Mixing Valve should be bypassing the Condenser to maintain head pres‐
sure. The inlet and outlet lines at the Condenser would be the same temp. in bypass mode. In
warmer ambients the Mixing Valve is pushing refrigerant to the Condenser Coil and there would
be approx. 20 degree F. temperature difference. A low charge would be identified by hot inlet
and outlet lines at the Condenser and a hot Receiver. Always verify charge before condemning
the Mixing Valve.
Содержание CIM Series
Страница 31: ...ELEVATION SERIES CIM CUBERS BOARD COMPONENT LED SEQUENCE 29 INITIAL HARVEST CYCLE AT START UP ...
Страница 32: ...ELEVATION SERIES CIM CUBERS BOARD COMPONENT LED SEQUENCE 30 TRANSITION FROM HARVEST TO FREEZE ...
Страница 33: ...ELEVATION SERIES CIM CUBERS BOARD COMPONENT LED SEQUENCE 31 BIN FULL CURTAIN OR STAT ...
Страница 35: ...ELEVATION SERIES CIM CUBERS BOARD COMPONENT LED SEQUENCE 33 DIAGNOSTICS IN HARVEST CYCLE ...
Страница 36: ...ELEVATION SERIES CIM CUBERS BUTTON FUNCTIONS 34 Button Functions ...
Страница 77: ...ELEVATION SERIES WIRING DIAGRAM 75 CIM220V 240V 50Hz SINGLE PHASE SINGLE EVAPORATOR REMOTE COOLED UINTS ...
Страница 78: ...ELEVATION SERIES WIRING DIAGRAM 76 CIM 230V 60Hz THREE PHASE SINGLE EVPAORATOR PLATE REMOTE COOLED UNITS ...
Страница 80: ...ELEVATION SERIES WIRING DIAGRAM 78 CIM 220V 240V 50Hz SINGLE PHASE DUAL EVAPORATOR AIR AND WATER COOLED UNITS ...
Страница 81: ...ELEVATION SERIES WIRING DIAGRAM 79 CIM 230V 60Hz THREE PHASE DUAL EVAPORATOR AIR AND WATER COOLED UNITS ...
Страница 82: ...ELEVATION SERIES WIRING DIAGRAM 80 CIM 115V and 230V 60Hz SINGLE PHASE DUAL EVAPORATOR REMOTE COOLED UNITS ...
Страница 83: ...ELEVATION SERIES WIRING DIAGRAM 81 CIM 220V 240V 50Hz SINGLE PHASE DUAL EVAPORATOR REMOTE COOLED UNITS ...
Страница 84: ...ELEVATION SERIES WIRING DIAGRAM 82 CIM 230V 60Hz THREE PHASE DUAL EVAPORATOR REMOTE COOLED UNITS ...