![ICC DNET-100 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/icc/dnet-100/dnet-100_user-manual_609876057.webp)
56
14.
Network-Specific Information
This section will discuss topics that are specific to each of the available
primary and secondary network selections.
14.1
DeviceNet (Primary) Network
•
Table 8 outlines the objects supported within the device. For more
specific details regarding the attributes and services supported by each
object, refer to the separately-provided ODVA Statement of Conformance
(SOC).
Table 8: Supported Objects
Object Class
# of Instances / Instance IDs
Class Code
Identity Object
1 / 1
0x01
Message Router
1 / 1
0x02
DeviceNet Object
1 / 1
0x03
Assembly Objects
4 / 100, 101, 150, 151
0x04
Connection Objects
3 / 1, 2, 4
0x05
Parameter Objects
User-defined / 1..100 max
0x0F
Acknowledge Handler
1 / 1
0x2B
•
All secondary network objects that are to be accessed must be defined as
DeviceNet parameters objects. Access is then available either via explicit
messaging or via membership in an IO assembly object.
•
DeviceNet object, BOI attribute: This attribute value is saved in the
gateway’s internal nonvolatile memory. If the BOI value is set to TRUE,
the gateway will attempt to restart the network interface on the occurrence
of a CAN bus-off event. This will continue to be the behavior until the Bus-
Off Counter attribute achieves a value of 255. If a CAN bus-off event
occurs after this point, the gateway will not attempt to restart the network
interface: it will remain faulted and isolated from the network until reset
(power removed from the unit or a console “exit” performed).
•
If any gateway characteristics are modified in the course of configuration,
remember to always download a new EDS file to your computer and re-
register it with your network configuration tool.
•
During I/O data exchanges, if the actual consumed data size is less than
or equal to the connection instance’s configured consumed connection
size, then all received data will be consumed and the connection will
produce normally. If the actual consumed data size is larger than the
Содержание DNET-100
Страница 8: ...7 2 Mechanical Diagrams 2 1 Enclosure Figure 2 Enclosure Dimensions units are inches ...
Страница 9: ...8 2 2 Mounting Clip Figure 3 Mounting Clip Dimensions units are inches ...
Страница 11: ...10 ASD Link LEDs Reserved LEDs ASD 2 ASD 3 ASD 1 Figure 6 Top View ...
Страница 38: ...37 Figure 13 HyperTerminal Configuration Screen 1 Figure 14 HyperTerminal Configuration Screen 2 ...
Страница 39: ...38 Figure 15 HyperTerminal Configuration Screen 3 ...
Страница 68: ...67 16 Notes ...
Страница 69: ...68 ...