SMALL FIRE PANEL IMC-MD
User manual
IMC-MD – User manual V190624
Page 13 of 51
3.1.3.1
Select test state
When the "D" button is pressed, the loops in the "TEST" state are displayed - see
tables 1-5 and 2-5.
At Access Level 3 the following commands are available to enable and disable the test
status (see also Table 3-4):
- On / off state "TEST" for the detector loop 1 - when the simultaneously "A" and
"D" buttons are pressed, the test state of the loop 1 is changed. When the
"LOOP1-
FAULT"
indicator is illuminated, the test status is active in the loop.
- On / off state "TEST" for the detector loop 2 - when the simultaneously "B" and
"D" buttons are pressed, the test state of the loop 2 is changed. When the
"LOOP2-
FAULT"
indicator is illuminated, the test status is active in the loop.
If any above mentioned part of the control panel is in the test state, the
"COMMON-
TEST"
indicator lights up on the access levels 1 and 2. The "TEST" status must be
manually terminated, it will not end automatically.
3.1.3.2
Disabling / enabling of delays
Delay switching on and off for individual parts of the control panel
When the "E" button is pressed the actual delayed parts of the control panel are
displayed on the indicators - see tables 1-3 and 2-3.
At Access Level 3 the following commands are available to enable and disable the
delays (see also Table 3-3):
- Activating / deactivating detector loop 1 start delay after switching on the loop
power supply (waiting for the detector parameters to stabilize) - when the "A" and "E"
buttons are pressed, the loop 1 start delay state is changed. If the
"LOOP1-FAULT"
indicator is lit, the loop delay after the start is on.
- Activating / deactivating detector loop 2 start delay after switching on the loop
power supply (waiting for the detector parameters to stabilize) - when the "B" and "E"
buttons are pressed, the loop 2 start delay state is changed. If the
"LOOP2-FAULT"
indicator is lit, the loop delay after the start is on.
- Activation / deactivation of the siren loop delay after the state change to the fire
alarm - when the "C" and "E" buttons are pressed, the state of the siren delay is changed.
If the
"SIREN-FAULT"
indicator is lit, the siren delay is on.
- Activation / deactivation of the siren function delay after the state change to the fire
alarm - when the "B", "C" and "E" buttons are pressed, the state of the siren delay is
changed. If the
"SIREN-FAULT"
indicator is lit, the siren delay is on.
- Activation / deactivation of the fire alarm ("FIRE") output delay after the alarm
state is active - when the "A", "B" and "E" buttons are pressed, the output delay state is
changed. When the
"OUTPUT-FIRE"
indicator is lit, the output delay is on.
- Activation / deactivation of the fault output ("FAULT") delay after the fault state is
active - when the "B", "C" and "E" buttons are pressed, the output delay state is changed.
When the
"OUTPUT-FAULT"
indicator is illuminated, the output delay is on.
If any above mentioned delay in the control panel is switched on, the
"COMMON-
DELAY"
indicator lights up on the access level 1.
3.1.3.3
Setting the length of delays
Pressing the "E" button and the delay button for the desired part of the control panel