SMALL FIRE PANEL IMC-MD
User manual
IMC-MD – User manual V190624
Page 5 of 51
of this output after the panel goes into the fire alarm state (access level 2) can be
enabled or disabled and the size of this delay can be set up to 10 minutes
(access level 3). When the delay is active, this delay can be bridged at access
level 1 and the FIRE output reacts immediately.
FAULT output can be disabled or enabled (access level 2). In addition the
delay of this output after the panel goes into the fault state (access level 2) can
be enabled or disabled and the size of this delay can be set up to 10 minutes
(access level 3).
1.3 Power
- Mains 230V / 50Hz, designed for a fixed installation
- Battery – protected Li-ion battery 3,6V, 2600mAh
1.4 Functions
- Silencing (and un-silencing) of acoustic indication of alarm and/or fault (internal
sounder, siren function, siren output)
- Siren function (increasing the voltage of the loops during an alarm that will trigger the
siren in the CHOR-E detectors)
- Canceling of fire alarm state and/or fault state
- Test state of individual loops (LOOP1, LOOP2)
- Disabling of individual loops (LOOP1, LOOP2 and LOOP SIR)
- Disabling of other parts (outputs FIRE, FAULT, internal buzzer, siren function)
- Test of all optic and acoustic indicators
- Initial delay after detectors loop power up for LOOP1 and LOOP2
- Delay for outputs SIREN, FIRE, FAULT, siren function
- Possibility of overriding active delay
- Possibility of a service key for input to the access levels 2 and 3
- Change of firmware (by external programmer on the access level 4)
- The possibility of one expansion module, now are available:
- Serial RS485 communication between other panels (IMC-MD,
μ
CU-IQ,
μ
CU-
LCD) – the RS485-MD module, no EN 54-2 compatible
- Auxiliary power supply 12V DC, 200mA from mains, from battery selectable
ON/OFF by a switch – the OPM1-MD module, no EN 54-2 compatible
1.5 Requirements for operators of the IMC-MD in terms of EN
62368-1 clause 0.2
- All work related to dismantling the panel cover (installation of the panel, the access
level 4 work) may only be performed by a skilled person. This requirement is specified for
all points of the user manual to which it relates.
- All panel control at the access levels 2 and 3 may only be performed by an instructed
person.
- The access level 1 control can be performed by anyone – an ordinary person.