Table 21. Power consumption
Number of modules
in the rack
Number of disk
drives
Model 281x-114 with
SSDs in kVA High
performance (1 and 2
TB / 3 TB)
Model 281x-214 with
SSDs in kVA High
performance (2 TB /
3 TB / 4 TB / 6 TB)
Model 281x-314 with
SSDs in kVA High
performance (4 TB /
6 TB)
6
72
2.9 / 2.9
2.5 / 2.6 / 2.6 / 2.6
N/A
9
108
4.3 / 4.2
3.6 / 3.8 / 3.9 / 3.9
4.7 / 4.7
10
120
4.7 / 4.7
4.0 / 4.2 / 4.3 / 4.3
5.1 / 5.1
11
132
5.1 / 5.2
4.3 / 4.5 / 4.6 / 4.6
5.5 / 5.5
12
144
5.5 / 5.7
4.7 / 4.9 / 5.0 /5.0
6.0 / 6.0
13
156
5.9 / 6.1
5.0 / 5.3 / 5.4 / 5.4
6.5 / 6.5
14
168
6.5 / 6.7
5.5 / 5.7 / 5.8 / 5.8
7.0 / 7.0
15
180
6.9 / 7.2
5.8 / 6.1 / 6.2 / 6.2
7.5 / 7.5
Input voltages and frequencies
This information lists the voltages or frequencies that are accepted by the IBM XIV
Storage System.
Table 22 provides the voltages and frequencies that are accepted by the XIV
system. For more information, see “Leakage current” on page xiii.
Table 22. Input voltages and frequencies
Characteristics
Voltage or frequency
Nominal input voltages
200, 220, or 240 V ac
Maximum input current
30 A or 60 A
Minimum input voltage
180 V ac
Maximum input voltage
264 V ac
Maximum ground-leakage current
0.3 A
Steady-state input frequencies
50±3 Hz or 60±3 Hz
Power line disturbance (PLD) input
frequencies
50±3 Hz or 60±3 Hz
Main-power cables specifications
Plan for power cable, connector, and receptacle requirements.
The XIV systems are available in multiple main-power cable configurations. The
automatic transfer switch (ATS) is chosen based on the required main-power
cables.
Attention:
The regional designations are general. The ATS assigned to the
regional designation might not be accurate for your country. If the input voltage
for the country uses a wye circuit, use the appropriate ATS and main-power cables
for EMEA (Europe, Middle East, and Africa) and Asia/Pacific. If input voltage for
the country uses a delta circuit, use the appropriate ATS and main-power cables
for United States, Canada, Latin America. For more information about electric
currents for various countries, see the International Trade Administration website
(http://www.trade.gov/mas/ian/ecw/all.html).
38
IBM XIV Gen3 281x-11x, 281x-21x, and 281x-314 Planning Guide
Содержание XIV Gen3 Series
Страница 1: ...IBM XIV Storage System Gen3 Models 281x 11x 281x 21x and 281x 314 Planning Guide SC27 5412 09 IBM...
Страница 6: ...vi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 8: ...viii IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 10: ...x IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 16: ...xvi IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 24: ...xxiv IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 52: ...28 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 87: ...AIX 7 Oracle Solaris 11 SPARC Solaris 11 INTEL HPUX HPUX 11i v3 IA64 Chapter 8 Management tool requirements 63...
Страница 88: ...64 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 94: ...70 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 116: ...92 IBM XIV Gen3 281x 11x 281x 21x and 281x 314 Planning Guide...
Страница 125: ......
Страница 126: ...IBM Printed in USA SC27 5412 09...