6.
Secure
the
electronics
module
to
the
uninterruptible
power
supply
chassis
with
the
screws
that
you
removed
in
step
4
on
page
36.
7.
Replace
the
front
bezel.
8.
Reconnect
any
cables
that
you
removed
in
step
1
on
page
36.
Replacing
the
battery
module
(for
trained
service
technician
only)
CAUTION:
Lead-acid
batteries
can
present
a
risk
of
electrical
burn
from
high,
short-circuit
current.
Avoid
battery
contact
with
metal
materials;
remove
watches,
rings,
or
other
metal
objects,
and
use
tools
with
insulated
handles.
To
avoid
possible
explosion,
do
not
burn.
Exchange
only
with
the
IBM-approved
part.
Recycle
or
discard
the
battery
as
instructed
by
local
regulations.
In
the
United
States,
IBM
has
a
process
for
the
collection
of
this
battery.
For
information,
call
1-800-426-4333.
Have
the
IBM
part
number
for
the
battery
unit
available
when
you
call.
(C004)
When
the
Battery
Service
LED
flashes
and
the
audible
alarm
beeps
once
every
five
seconds,
you
might
need
to
replace
the
battery
module.
Contact
your
technical-support
representative
to
order
new
batteries.
Important:
Do
not
disconnect
the
batteries
while
the
uninterruptible
power
supply
is
in
Battery
mode.
Consider
all
warnings,
cautions,
and
notes
before
replacing
batteries.
With
the
hot-swappable
battery
feature,
uninterruptible
power
supply
batteries
can
be
replaced
without
turning
the
uninterruptible
power
supply
off
or
disconnecting
the
load.
If
you
want
to
remove
input
power
to
change
the
battery,
complete
the
following
steps:
1.
Press
and
hold
the
Off
button
until
the
long
beep
ceases
(approximately
five
seconds),
and
then
disconnect
the
uninterruptible
power
supply.
2.
Wait
60
seconds
while
the
internal
processor
shuts
down
before
you
disconnect
the
battery.
To
replace
the
battery
module,
complete
the
following
steps.
You
will
need
a
5/16-inch
wrench
to
remove
the
battery
module.
1.
If
the
uninterruptible
power
supply
is
installed
in
a
rack,
remove
the
uninterruptible
power
supply
from
the
rack
and
set
it
on
a
level
surface.
2.
To
remove
the
uninterruptible
power
supply
bezel,
grasp
the
left
and
right
sides
of
the
bezel
and
pull
it
off
Chapter
5.
Hardware
maintenance
information
37
Содержание UPS3000 HV
Страница 1: ...UPS3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 2: ......
Страница 3: ...UPS3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 28: ...16 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 36: ...24 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 46: ...34 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 54: ...42 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 80: ...68 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Страница 83: ......
Страница 84: ... Part Number 40K9691 Printed in USA 1P P N 40K9691 ...