14
3: U
SER
C
ONFIGURABLE
I
TEMS
N
OTE
:
S
ETTINGS ARE MADE THROUGH THE SUPPLIED
P
OWER
C
HUTE
B
USINESS
E
DITION SOFTWARE
, N
ETWORK
M
ANAGEMENT
C
ARD
,
OR TERMINAL MODE
. R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Automatic Self-Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test
This function sets the interval at which
the uninterruptible power supply will
execute a self-test.
Uninterruptible
Power Supply ID
UPS_IDEN
Up to eight characters
Use this field to uniquely identify the
uninterruptible power supply, (i.e.
server name or location) for network
management purposes.
Date of Last Battery
Replacement
Manufacture Date
mm/dd/yy
Reset this date when you replace the
battery modules.
Minimum Capacity
Before Return from
Shutdown
0 percent
0, 15, 25, 35, 50, 60,
75, 90 percent
The uninterruptible power supply will
charge its batteries to the specified
percentage before it powers up con-
nected equipment, following a low-
battery shutdown.
Alarm Delay After
Line Failure
5 second delay
5 second delay,
30 second delay,
At Low Battery,
Never
The user can mute an ongoing alarm or
disable all existing alarms permanently.
Shutdown Delay
20 seconds
0, 20, 60, 120, 240,
480, 720, 960 sec-
onds
The interval is set between the times
when the uninterruptible power supply
receives a shutdown command and
actual shutdown.
Duration of Low
Battery Warning
2 minutes
(PowerChute soft-
ware provides
automatic, unat-
tended shutdown
when approxi-
mately two min-
utes of battery
runtime remain.)
2, 5, 7, 10, 12, 15, 18,
20 minutes
The low battery warning beeps become
continuous when two minutes of run-
time remain.
Change the warning interval to a higher
setting if the operating system requires
a longer interval for shutdown.
Synchronized Turn-
on Delay
0 seconds
0, 20, 60, 120, 240,
480, 720, 960 sec-
onds
The uninterruptible power supply will
wait the specified time after the return
of utility power before turn-on (to
avoid branch circuit overload).
High Bypass Point
+10% of output
voltage setting
+5%, +10%, +15%,
+20%
The uninterruptible power supply will
pass this maximum voltage to con-
nected equipment during internal by-
pass operation.
Low Bypass Point
-30% of output
voltage setting
-15%, -20%, -25%,
-30%
The uninterruptible power supply will
pass this minimum voltage to con-
nected equipment during internal by-
pass operation.
Output Voltage
230 Vac
200, 208, 220, 230,
240 Vac
The user is able to select the uninter-
ruptible power supply output voltage
while online. Use the voltage setting
applicable to your region.