![IBM UPS 7500XHV Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/ibm/ups-7500xhv/ups-7500xhv_operation-and-setup-manual_3385729014.webp)
10
Selecting the Output Voltage via Terminal Mode
Terminal Mode is a menu driven interface that enables enhanced configuration of the uninterruptible power supply.
Connect the serial cable to the serial port on the back of the uninterruptible power supply.
When using the PowerChute
®
Network Shutdown utility:
1. Exit the PowerChute Business Edition agent and server
using the following steps:
a. From the desktop, click
Start
=>
Settings
=>
Control Panel
=>
Administrative Tools
=>
Services
.
b. Select
PCBE Server and PCBE Agent
; then, right click the mouse and select
Stop
.
2. Open a terminal program, for example HyperTerminal.
From the desktop, click
Start
=>
Programs
=>
Accessories
=>
Communication
=>
HyperTerminal.
3. Double-click on the
HyperTerminal
icon.
a. Follow the prompts to choose a name and select an icon. Disregard the message,
must install a modem
, if it is dis-
played. Click
OK
.
b. Select the
COM
port that is connected to your uninterruptible power supply. The port settings are:
bits per second - 2400
data - bits 8
parity - none
stop bit - 1
flow control - none
c. Click Enter.
4. Once the blank terminal window is open, follow these steps to configure the output voltage:
a. Press Enter to initiate terminal mode. Press Enter multiple times, until the
User Name
prompt is displayed. Follow the
prompts. Type slowly, waiting until each character is displayed on the screen before typing the next character.
Network Management Card defaults:
•
User Name:
apc
•
Password:
apc
b. Press 1 and Enter to select
Device Manager
.
Select the number corresponding to the desired model and press Enter.
c. Press 3 and Enter to select
Configuration
.
d. Press 2 and Enter to select
Line Transfer
.
e. Press 3 and Enter to select
Output Voltage
.
Select the number corresponding to the desired voltage setting and press Enter.
f. Press 5 and Enter to
Accept Changes
.
g. Press Esc multiple times to return to the main menu.
h. Press 4 and Enter to log out.
Содержание UPS 7500XHV