Table 38. Power consumption and cooling requirements for TS4500 tape library frame models
Description
Power consumption (Watts)
Cooling
Requirements
(Btu per hr,
maximum
continuous)
2
Off
1
Idle
Maximum
continuous
(not peak)
MODELS
L25, L55
3, 4
11
95
130
443
D25, D55, S25, S55
3, 5
0
11
11
38
FEATURE CODES
FC 1442 HA Kit w/Second Accessor
0
24
85
290
FC 1450 (TS4500 FCA) including
one LCC and two AC/DC power supplies
11
38
38
130
FC 1460 (second LFI for Lx5 frame
in a multiple frame network)
0
5
5
17
FC 1521, 1523, 1524
(quad drive mounting kits)
0
3
3
10
FC 1751 PDU
(for TR1 top rack)
9
9
9
31
FC 1951 PDU
17
17
17
58
RPQ 8B3683
0
65
2051
6994
TAPE DRIVES
TS1140 drive (3592 EH7)
6
0
28
50
171
TS1150 drive (3592 EH8)
6
0
23
48
164
TS1155 drive (3592 55F)
6
0
23
48
164
TS1155 drive (3592 55E)
6
0
50
63
215
TS1050 drive (LTO 3588 F5C)
6
0
16
32
109
TS1060 drive (LTO 3588 F6C)
6
0
13
36
123
TS1070 drive (LTO 3588 F7C)
6
0
15
31
106
TS1080 drive (LTO 3588 F8C)
6
0
15
31
106
Notes:
1.
"Off" refers to power consumed when the library is connected to an AC power source and the library on/off
switch is set to off.
2.
To calculate the total cooling that is required by the library (in Btu per hr), multiply the total power in watts by
3.41. To convert
Btu per hr
to
kBtu per hr
, divide your result by 1000.
3.
Lx5 models and models with FC 1450 or FC1951 come equipped with dual AC power cords. The figures in the
table show the total power that is consumed, including power that is consumed by redundant power supplies.
Each power cord supplies approximately half of the power.
4.
Lx5 frame power includes all frame loads, cartridge accessor, IMC, and display.
5.
For base models that do not include FC 1450 (TS4500 FCA), the power consumption that is shown in the table
figures is power that is provided by other frames. The figures include power consumption for the lighting and
two LFIs.
6.
Idle power is consumed when the drive has no tape cartridge loaded. Maximum continuous power is consumed
when the drive is actively reading and writing to the tape. The power consumption that is shown in the table
figures includes the power that is required for the cooling fan at normal speed. In ambient environments that are
hotter than the recommended range, the cooling fan might speed up and draw more power.
Chapter 2. Planning
93
Содержание TS4500
Страница 1: ...IBM TS4500 Introduction and Planning Guide EC SC27 5990 06 IBM...
Страница 4: ...iv IBM TS4500 Introduction and Planning Guide...
Страница 8: ...viii IBM TS4500 Introduction and Planning Guide...
Страница 10: ...x IBM TS4500 Introduction and Planning Guide...
Страница 12: ...xii IBM TS4500 Introduction and Planning Guide...
Страница 49: ...2 and 4 Figure 9 B accessor in Service Bay B Chapter 1 Overview 31...
Страница 88: ...70 IBM TS4500 Introduction and Planning Guide...
Страница 99: ...Figure 17 Access panel for Fibre Channel and Ethernet cable routing Chapter 2 Planning 81...
Страница 186: ...Korea Notice Russia Notice 168 IBM TS4500 Introduction and Planning Guide...
Страница 217: ......
Страница 218: ...IBM Printed in USA...