80010701-1404ffff
Numeric sensor [NumericSensorElementName] going high (upper non-critical) has asserted.
(DIMM CD VR Temp)
Explanation:
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107011404ffff or 0x800107011404ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0490
SNMP Trap ID:
12
Automatically notify Support:
No
User response:
1.
Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of the server),
that the air baffle is in place and correctly installed, and that the server cover is installed and completely closed.
2.
Check the ambient temperature. You must be operating within the specifications (see Server Features and
specifications for more information).
3.
Make sure that the heat sink for microprocessor n.
4.
(Trained technician only) Replace system board.
80010701-1405ffff
Numeric sensor [NumericSensorElementName] going high (upper non-critical) has asserted.
(DIMM EF VR Temp)
Explanation:
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107011405ffff or 0x800107011405ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0490
SNMP Trap ID:
12
Automatically notify Support:
No
User response:
1.
Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of the server),
that the air baffle is in place and correctly installed, and that the server cover is installed and completely closed.
2.
Check the ambient temperature. You must be operating within the specifications (see Server Features and
specifications for more information).
3.
Make sure that the heat sink for microprocessor n.
4.
(Trained technician only) Replace system board.
80010701-1404ffff • 80010701-1405ffff
Appendix A. Integrated management module II (IMM2) error messages
327
Содержание System x3650 M4 BD Type 5466
Страница 1: ...System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 8: ...vi System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 102: ...86 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 130: ...114 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 178: ...162 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 189: ...v Type 2 SAS Figure 84 Cable routing Chapter 6 Removing and replacing components 173 ...
Страница 606: ...590 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 766: ...750 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 775: ...Taiwan Class A compliance statement Notices 759 ...
Страница 776: ...760 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 778: ...762 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 784: ...768 System x3650 M4 BD Type 5466 Installation and Service Guide ...
Страница 785: ......
Страница 786: ... Part Number 00KC029 Printed in USA 1P P N 00KC029 ...