In this section, you need to remove the enclosure and its respective rails and
relocate them in the desired location. The enclosure rails differ from those of the
file modules.
Review the documentation that comes with the rack cabinet for safety and the
cabling information. Before you begin, review the following guidelines
v
Two or more people are required to install devices 2U or larger in a rack cabinet.
v
Make sure that the room air temperature is below 35°C (95°F).
v
Do not block any air vents; usually 15 cm (6 inch) of space provides proper
airflow.
v
Do not leave open spaces above or below an installed control enclosure in the
rack cabinet. To help prevent damage to control enclosure components, always
install a blank filler panel to cover the open space and to help ensure proper air
circulation. Install the control enclosure only in a rack cabinet with perforated
doors.
v
Plan the device installation starting from the bottom of the rack cabinet.
v
Install the heaviest device in the bottom of the rack cabinet.
v
Do not extend more than one device out of the rack cabinet at the same time.
v
Remove the rack doors and side panels to provide easier access during
installation.
v
Connect the control enclosure to a properly grounded outlet.
v
Do not overload the power outlet when you install multiple devices in the rack
cabinet.
v
Install the control enclosure in a rack that meets the following requirements:
– Minimum depth of 70 mm (2.76 inch) between the front mounting flange and
inside of the front door.
– Minimum depth of 157 mm (6.18 inch) between the rear mounting flange and
inside of the rear door.
svc00688
Figure 26. Securing an enclosure to a rack cabinet
72
IBM Storwize V7000 Unified: Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073-720
Содержание Storwize V7000
Страница 20: ...xx IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 60: ...40 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 88: ...68 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 128: ...108 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 132: ...112 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 138: ...118 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 142: ...122 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 150: ...130 IBM Storwize V7000 Unified Adding Storwize V7000 File Modules to an existing Storwize V7000 system 2073 720...
Страница 151: ......
Страница 152: ...Part Number 00MJ333 Printed in USA SC27 4223 05 1P P N 00MJ333...