Appendix C. UPS runtime estimate (minutes)
511
Notes:
1.
Data provided by Eaton.
Table 147. IBM UPS3000HV Runtimes
1
Number of Battery Packs
+0
+1
+2
+3
+4
Total Load
(Watts)
Runtime
(Hours / Minutes)
Runtime
(Hours/ Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
200
1/3
4/38
9/5
12/48
16/42
300
55
4/5
8/0
11/16
14/42
400
48
3/33
6/59
9/59
12/50
500
42
3/6
6/4
8/33
11/10
600
36
2/38
5/10
7/17
9/30
700
31
2/14
4/23
6/11
8/4
800
26
1/56
3/48
5/22
7/0
900
23
1/40
3/16
4/36
6/0
1000
19
1/23
2/44
3/51
5/2
1100
16
1/12
2/22
3/20
4/22
1200
14
1/3
2/4
2/54
3/48
1300
12
55
1/48
2/33
3/20
1400
10
47
1/32
2/10
2/50
1500
9
45
1/28
2/4
2/42
1600
9
41
1/20
1/53
2/28
1700
8
40
1/18
1/50
2/24
1800
8
40
1/18
1/50
2/24
1900
7
35
1/8
1/36
2/6
2000
7
35
1/8
1/36
2/6
2100
7
33
1/5
1/32
2/0
2200
6
30
58
1/22
1/48
2300
6
30
58
1/22
1/48
2400
6
30
58
1/22
1/48
2500
6
26
51
1/12
1/34
2600
5
25
49
1/9
1/30
2700
5
25
49
1/9
1/30
Содержание SCOD-3ZVQ5W
Страница 6: ...vi COG ...
Страница 22: ...14 COG ...
Страница 32: ...24 COG Figure 5 Z Pro 6223 Rear View ...
Страница 36: ...28 COG ...
Страница 40: ...32 COG Figure 6 Z Pro 9228 memory DIMMs ...
Страница 46: ...38 COG ...
Страница 53: ...Chapter 4 IntelliStation A Pro 6217 45 Figure 8 A Pro 6217 system board ...
Страница 58: ...50 COG ...
Страница 80: ...72 COG Figure 14 x206m rear view ...
Страница 102: ...94 COG Figure 19 xSeries 226 rear view ...
Страница 109: ...Chapter 7 xSeries 226 101 Notes 1 Installation may require removing a standard device ...
Страница 110: ...102 COG ...
Страница 134: ...126 COG ...
Страница 148: ...140 COG ...
Страница 168: ...160 COG ...
Страница 182: ...174 COG ...
Страница 188: ...180 COG Figure 32 x3500 system board ...
Страница 198: ...190 COG ...
Страница 203: ...Chapter 15 System x3550 195 Figure 33 x3550 system board ...
Страница 213: ...Chapter 15 System x3550 205 ...
Страница 214: ...206 COG ...
Страница 226: ...218 COG ...
Страница 240: ...232 COG ...
Страница 265: ...Chapter 20 System x3950 and xSeries 460 257 Figure 46 x3950 and x460 rear view Figure 47 x3950 and x460 system board ...
Страница 272: ...264 COG ...
Страница 275: ...Chapter 21 Datacenter solution program 267 Datacenter solutions ...
Страница 294: ...286 COG ...
Страница 312: ...304 COG ...
Страница 320: ...312 COG ...
Страница 327: ...Chapter 25 BladeCenter chassis 8677 319 Figure 72 8677 rear view Figure 73 8677 switch module bays ...
Страница 336: ...328 COG Figure 81 BladeCenter H 8852 rear view ...
Страница 338: ...330 COG ...
Страница 344: ...336 COG ...
Страница 352: ...344 COG ...
Страница 360: ...352 COG ...
Страница 364: ...356 COG ...
Страница 374: ...366 COG ...
Страница 378: ...370 COG ...
Страница 400: ...392 COG ...
Страница 436: ...428 COG ...
Страница 446: ...438 COG ...
Страница 450: ...442 COG ...
Страница 454: ...446 COG ...
Страница 464: ...456 COG ...
Страница 491: ...Chapter 55 xSeries rack power configurator 483 ...
Страница 495: ...Chapter 55 xSeries rack power configurator 487 ...
Страница 501: ... Copyright IBM Corp 2003 2006 493 Part 2 Appendixes ...
Страница 502: ...494 COG ...
Страница 530: ...522 COG ...
Страница 534: ...526 COG ...
Страница 542: ...534 COG ...
Страница 544: ...536 COG ...
Страница 547: ......
Страница 548: ...IBM Printed in USA SCOD 3ZVQ5W 07SCOD3ZVQ5W ...