Appendix C. UPS runtime estimate (minutes)
Steps to determine UPS runtimes and suitable UPS for desired configurations:
1.
Using the 'Power Load Data' table, sum the load (watts) of all devices in the configuration. Use either
Maximum Load for minimum runtimes, or Typical Load for typical runtimes.
2.
Using the 'Runtimes' table, locate the configuration's total load calculated in step 1.
3.
Select the most appropriate UPS model to achieve the desired runtime.
Note:
If the configuration's total load is greater than the entries in the 'Runtimes' table, split the load across
two or more UPS units.
Table 143. Power Load Data
Server
Number of Power Cords (Std/Max)
Watts Load
(Typical/Max)
1
xSeries 206m
2
2/2
246/352
xSeries 226 (single power supply)
2
1/1
495/707
xSeries 226 (redundant power supplies)
2
2/2
480/685
xSeries 236
2
1/2
625/893
xSeries 260 (two power supplies)
2
2/3
679/970
xSeries 260 (three power supplies)
2
2/3
1288/1840
xSeries 306m
2
1/1
350/500
xSeries 306
2
1/1
300/430
xSeries 336
2
1/2
385/550
xSeries 346
2
1/2
581/830
System x3850 and xSeries 366
2
1/2
1103/1575
System x3950 and xSeries 460
2
2/2
1103/1575
eServer 326m
2
1/1
280/400
x3400 entry
2
1/1
463/662
x3550
2
1/2
490/700
x3650
2
1/2
679/970
x3800 (two power supplies)
2
2/3
679/970
x3800 (three power supplies)
2
2/3
1288/1840
x3850
2
2/2
1103/1575
x3950
2
2/2
1103/1575
BladeCenter (two 2000W power supplies)
2, 3
2/4
1855/2650
BladeCenter (four 2000W power supplies)
2, 3
4/4
3710/5300
BladeCenter H (two 2900W power supplies)
2, 3
2/2
3325/4750
BladeCenter H (four 2900W power supplies)
2, 3
4/4
6650/9500
Other Devices
EXP400 Storage Expansion Unit (17331RU)
2
2/2
310/440
Содержание SCOD-3ZVQ5W
Страница 6: ...vi COG ...
Страница 22: ...14 COG ...
Страница 32: ...24 COG Figure 5 Z Pro 6223 Rear View ...
Страница 36: ...28 COG ...
Страница 40: ...32 COG Figure 6 Z Pro 9228 memory DIMMs ...
Страница 46: ...38 COG ...
Страница 53: ...Chapter 4 IntelliStation A Pro 6217 45 Figure 8 A Pro 6217 system board ...
Страница 58: ...50 COG ...
Страница 80: ...72 COG Figure 14 x206m rear view ...
Страница 102: ...94 COG Figure 19 xSeries 226 rear view ...
Страница 109: ...Chapter 7 xSeries 226 101 Notes 1 Installation may require removing a standard device ...
Страница 110: ...102 COG ...
Страница 134: ...126 COG ...
Страница 148: ...140 COG ...
Страница 168: ...160 COG ...
Страница 182: ...174 COG ...
Страница 188: ...180 COG Figure 32 x3500 system board ...
Страница 198: ...190 COG ...
Страница 203: ...Chapter 15 System x3550 195 Figure 33 x3550 system board ...
Страница 213: ...Chapter 15 System x3550 205 ...
Страница 214: ...206 COG ...
Страница 226: ...218 COG ...
Страница 240: ...232 COG ...
Страница 265: ...Chapter 20 System x3950 and xSeries 460 257 Figure 46 x3950 and x460 rear view Figure 47 x3950 and x460 system board ...
Страница 272: ...264 COG ...
Страница 275: ...Chapter 21 Datacenter solution program 267 Datacenter solutions ...
Страница 294: ...286 COG ...
Страница 312: ...304 COG ...
Страница 320: ...312 COG ...
Страница 327: ...Chapter 25 BladeCenter chassis 8677 319 Figure 72 8677 rear view Figure 73 8677 switch module bays ...
Страница 336: ...328 COG Figure 81 BladeCenter H 8852 rear view ...
Страница 338: ...330 COG ...
Страница 344: ...336 COG ...
Страница 352: ...344 COG ...
Страница 360: ...352 COG ...
Страница 364: ...356 COG ...
Страница 374: ...366 COG ...
Страница 378: ...370 COG ...
Страница 400: ...392 COG ...
Страница 436: ...428 COG ...
Страница 446: ...438 COG ...
Страница 450: ...442 COG ...
Страница 454: ...446 COG ...
Страница 464: ...456 COG ...
Страница 491: ...Chapter 55 xSeries rack power configurator 483 ...
Страница 495: ...Chapter 55 xSeries rack power configurator 487 ...
Страница 501: ... Copyright IBM Corp 2003 2006 493 Part 2 Appendixes ...
Страница 502: ...494 COG ...
Страница 530: ...522 COG ...
Страница 534: ...526 COG ...
Страница 542: ...534 COG ...
Страница 544: ...536 COG ...
Страница 547: ......
Страница 548: ...IBM Printed in USA SCOD 3ZVQ5W 07SCOD3ZVQ5W ...