Upgrade calculation
To determine the power-module capacity that is needed to maintain full redundancy in each power domain,
complete the following steps.
If you have two 2000 W power modules installed in power domain A and two 2000 W power modules
installed in power domain B, you do not need to complete this upgrade calculation. Your system meets the
requirements to maintain full power redundancy in both domains.
Attention:
If you are replacing the existing power modules with 2000 W power modules, you must upgrade
the management-module firmware. If two management modules are installed in the BladeCenter unit, both
management modules must be upgraded to the same level of firmware. Go to the IBM Support Web site at
http://www.ibm.com/support/ and obtain the latest firmware.
1.
In the power worksheets on page 532, list the blade servers or other devices that are installed in the bays.
2.
In the tables on page 529, look up the number of IBM power units associated with each device and enter
it in the applicable power worksheet (see “Example calculation” on page 532).
3.
Add all of the IBM power unit values for each domain and enter the totals.
4.
To maintain full power redundancy in power domain A, make sure that the power modules in bays 1
and 2 are connected to different 200 - 240 volt ac power sources and meet the requirements in the
following table:
Table 155. JS20 blade server power values
BladeCenter JS20 blade server
IBM power units for two
installed microprocessors
1.6 GHz/800 MHz (8842-21X)
1.5
2.2 GHz/1.1GHz (8842-41X)
1.6
Table 156. LS20 blade server power values
BladeCenter LS20 blade server
IBM power units for the corresponding
number of installed microprocessors
1 microprocessor
2 microprocessors
2.0 to 2.6 GHz Single Core (8850-51X, 8850-71X, 8850-81X)
1.2
1.8
2.0 GHz Dual Core (8850-55x)
1.2
1.8
Table 157. BladeCenter expansion unit power values
BladeCenter Expansion unit
1
IBM power units
SCSI Storage Expansion Unit, SCSI Storage Expansion Unit 2
0.4
Содержание SCOD-3ZVQ5W
Страница 6: ...vi COG ...
Страница 22: ...14 COG ...
Страница 32: ...24 COG Figure 5 Z Pro 6223 Rear View ...
Страница 36: ...28 COG ...
Страница 40: ...32 COG Figure 6 Z Pro 9228 memory DIMMs ...
Страница 46: ...38 COG ...
Страница 53: ...Chapter 4 IntelliStation A Pro 6217 45 Figure 8 A Pro 6217 system board ...
Страница 58: ...50 COG ...
Страница 80: ...72 COG Figure 14 x206m rear view ...
Страница 102: ...94 COG Figure 19 xSeries 226 rear view ...
Страница 109: ...Chapter 7 xSeries 226 101 Notes 1 Installation may require removing a standard device ...
Страница 110: ...102 COG ...
Страница 134: ...126 COG ...
Страница 148: ...140 COG ...
Страница 168: ...160 COG ...
Страница 182: ...174 COG ...
Страница 188: ...180 COG Figure 32 x3500 system board ...
Страница 198: ...190 COG ...
Страница 203: ...Chapter 15 System x3550 195 Figure 33 x3550 system board ...
Страница 213: ...Chapter 15 System x3550 205 ...
Страница 214: ...206 COG ...
Страница 226: ...218 COG ...
Страница 240: ...232 COG ...
Страница 265: ...Chapter 20 System x3950 and xSeries 460 257 Figure 46 x3950 and x460 rear view Figure 47 x3950 and x460 system board ...
Страница 272: ...264 COG ...
Страница 275: ...Chapter 21 Datacenter solution program 267 Datacenter solutions ...
Страница 294: ...286 COG ...
Страница 312: ...304 COG ...
Страница 320: ...312 COG ...
Страница 327: ...Chapter 25 BladeCenter chassis 8677 319 Figure 72 8677 rear view Figure 73 8677 switch module bays ...
Страница 336: ...328 COG Figure 81 BladeCenter H 8852 rear view ...
Страница 338: ...330 COG ...
Страница 344: ...336 COG ...
Страница 352: ...344 COG ...
Страница 360: ...352 COG ...
Страница 364: ...356 COG ...
Страница 374: ...366 COG ...
Страница 378: ...370 COG ...
Страница 400: ...392 COG ...
Страница 436: ...428 COG ...
Страница 446: ...438 COG ...
Страница 450: ...442 COG ...
Страница 454: ...446 COG ...
Страница 464: ...456 COG ...
Страница 491: ...Chapter 55 xSeries rack power configurator 483 ...
Страница 495: ...Chapter 55 xSeries rack power configurator 487 ...
Страница 501: ... Copyright IBM Corp 2003 2006 493 Part 2 Appendixes ...
Страница 502: ...494 COG ...
Страница 530: ...522 COG ...
Страница 534: ...526 COG ...
Страница 542: ...534 COG ...
Страница 544: ...536 COG ...
Страница 547: ......
Страница 548: ...IBM Printed in USA SCOD 3ZVQ5W 07SCOD3ZVQ5W ...