Table 8. Temperature and humidity requirements for storage subsystem in a NEBS/ETSI
compliant environment (continued)
Condition
Parameter
Requirement
Notes:
1.
In a NEBS/ETSI compliant environment, conditions are measured at a location 1.5 m (59
in.) above the floor and 400 mm (15.8 in.) in front of the equipment.
2.
Short-term refers to a period of not more than 96 consecutive hours and a total of not
more than 15 days in one year. (This refers to a total of 360 hours in any given year, but
no more than 15 occurrences during that one-year period.)
Altitude
Table 9 lists the acceptable altitudes for operating, storing, and shipping the
DS3950.
Table 9. DS3950 altitude ranges
Environment
Altitude
Operating
30.5 m (100 ft.) below sea level to 3000 m
(9842 ft.) above sea level
Storage
30.5 m (100 ft.) below sea level to 3000 m
(9842 ft.) above sea level
Transit
30.5 m (100 ft.) below sea level to 12,000 m
(40,000 ft.) above sea level
Airflow and heat dissipation
Figure 9 shows the intended airflow for the DS3950. Allow at least 30 inches in
front of the storage subsystem and at least 24 inches behind the storage subsystem
for service clearance, proper ventilation, and heat dissipation.
Table 10 on page 23 lists the KVA, watts, and Btu calculations. These values
assume the power supplies have a 73 percent efficiency and a power factor of 0.99.
These tabulated power and heat dissipation values are typical for the storage
subsystem. Maximum configuration units are typically operated at higher data
rates, have larger random access memory (RAM) capacities, or have different host
interface boards.
Figure 9. DS3950 airflow
22
IBM System Storage DS3950 Storage Subsystem: Installation, User’s, and Maintenance Guide
Содержание DS3950
Страница 1: ...IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide GA32 0953 03...
Страница 2: ......
Страница 3: ...IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide GA32 0953 03...
Страница 8: ...vi IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 12: ...x IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 28: ...xxvi IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 54: ...26 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 148: ...120 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 202: ...174 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 210: ...182 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 214: ...186 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 226: ...198 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 246: ...218 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 250: ...222 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Страница 251: ......
Страница 252: ...Part Number 00Y5046 Printed in USA GA32 0953 03 1P P N 00Y5046...