Nut
Flat washer
(optional)
Split washer
When
connecting
a
wire
to
each
stud,
install
a
flat
washer
(optional)
on
the
stud,
install
the
wire,
install
a
flat
washer
(optional),
install
a
split
washer
and
then
install
the
nut.
The
following
guidelines
are
provided
for
connecting
a
60
A
BladeCenter
HT
unit
to
a
-48
V
dc
power
source:
v
The
power
source
must
have
a
minimum
of
80
A
overcurrent
protection.
See
article
240,
paragraph
3,
table
310-16
of
the
National
Electric
Code
for
more
information
about
electrical
wiring
requirements.
v
The
overcurrent
protective
device
or
circuit
breaker
must
be
accessible
to
service
personnel
to
prevent
the
power
from
being
turned
on
by
someone
other
than
the
technician
servicing
the
BladeCenter
HT
unit.
v
The
BladeCenter
HT
unit
has
a
dc
wire
rating
of
4
AWG
(circular
mil
area
of
33100-52600)
and
rated
90
degree
C.
Note:
The
actual
wire
gauge
and
ring
terminal
will
be
determined
by
the
current
draw
and
the
length
of
wire
run
or
as
specified
by
the
customer
premises
guidelines.
v
Flexible
dc
wiring
is
recommended
to
allow
for
minimum
bend
radius.
v
The
supply
wiring
to
the
power
connectors
must
be
terminated
in
UL
recognized
insulated
ring
terminals,
sized
for
a
M6
stud,
4
AWG
wire
(circular
mil
area
of
33100-52600)
and
a
wire
insulation
diameter
of
12.8
to
13.1
mm.
An
example
of
this
type
of
ring
terminal
is
Amp
Plasti-Grip
type
52043–1
using
Tyco
Electronics
Hydraulic
Crimping
Tool
part
number
1490749–1.
v
For
NEBS
compliance,
the
protective
earthing
conductor
must
use
copper
conductors
with
a
size
minimum
of
6
AWG
(circular
mil
area
of
20800–33100)
and
must
be
terminated
in
a
UL
recognized
two
hole
lug
sized
for
a
M6
stud.
Chassis
ground
studs
are
on
5/8-inch
centers.
An
example
of
this
type
of
two
hole
lug
is
the
Thomas
and
Betts
part
number
54205
using
the
Thomas
and
Betts
crimping
tool
model
TBM-25S.
v
Torque
the
wiring-terminal
nuts
to
1.5
newton-meters
(13.3
inch-pounds)
For
more
information,
see
Statement
34
in
“Safety”
on
page
vii.
Chapter
2.
BladeCenter
HT
unit
power,
components,
and
indicators
15
Содержание 87401RU
Страница 3: ...BladeCenter HT Type 8740 and 8750 Installation and User s Guide...
Страница 8: ...vi BladeCenter HT Type 8740 and 8750 Installation and User s Guide...
Страница 82: ...66 BladeCenter HT Type 8740 and 8750 Installation and User s Guide...
Страница 92: ...76 BladeCenter HT Type 8740 and 8750 Installation and User s Guide...
Страница 108: ...92 BladeCenter HT Type 8740 and 8750 Installation and User s Guide...
Страница 109: ......
Страница 110: ...Part Number 44R5188 Printed in USA 1P P N 44R5188...