6
2: I
NSTALLATION
DANGER
Energy hazard present. Shorting might result in system outage and possible physical injury.
Remove all metallic jelewlry before servicing. (C001)
Removing the Battery Modules
The battery pack is heavy. Remove the battery modules to lighten the weight of the unit.
X
Remove the nine screws that secure the
battery compartment door.
Y
Remove the battery modules.
Specifications
Operation
0° to 40° C (32° to 104° F)
Temperature
Storage
-15° to 30° C (5° to 86° F)
charge the UPS battery every six months
30° to 45° C (86° to 113° F)
charge the UPS battery every three months
Operating
3,000 m (10,000 ft)
Maximum
Elevation
Storage
15,000 m (50,000 ft)
Humidity
0 to 95% relative humidity
This unit is intended for indoor use only. Select a
location sturdy enough to handle the weight.
Do not operate the unit where there is excessive dust
or the temperature and humidity are outside the
specified limits.
Be sure that the air vents on the front and rear of
the unit are not blocked. Allow adequate space for
proper ventilation.
Environmental factors impact battery life. High
temperatures, poor utility power, and frequent, short
duration discharges will shorten battery life.
CAUTION
or
>32 kg (70.5 lb)
or
32-55 kg (70.5-121.2 lb)
The weight of this part or unit is between 32 and 55 kg (70.5 and 121.2 lb). It takes three persons to safely lift this unit. (C010)