Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
See Chapter 4, “Parts listing,” on page 41 to determine which components are CRUs and which components
are FRUs.
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Lit light path
diagnostics LED
Description
Action
Microprocessor
error
The microprocessor has failed or overheated,
or the start microprocessor is missing.
1.
Check the AMM event logs.
2.
If the log shows that a microprocessor is
disabled or that a microprocessor error has
occurred, perform one of the following
actions:
a.
(Trained service technician only) Reseat
the microprocessor that is indicated by
the lit LED. See “Removing a
microprocessor and heat sink” on page
90 and “Installing a microprocessor and
heat sink” on page 94.
b.
(Trained service technician only)
Replace the microprocessor that is
indicated by the lit LED. See
“Removing a microprocessor and heat
sink” on page 90 and “Installing a
microprocessor and heat sink” on page
94.
MIS
Microprocessor mismatch.
Make sure that microprocessors 1 and 2 are
identical (number of cores, cache size and
type, clock speed, internal and external clock
frequencies).
1.
Verify the type of microprocessors installed
by using the Configuration/Setup utility.
See “Using the Setup utility” on page 21.
2.
(Trained service technician only) Replace
microprocessor 2 with an identical
microprocessor to microprocessor 1. See
“Removing a microprocessor and heat
sink” on page 90 and “Installing a
microprocessor and heat sink” on page 94.
NMI (NMI error)
The system board has failed.
1.
Replace the blade server cover, reinsert the
blade server in the BladeCenter unit, and
then restart the blade server. Check the
BMC log for information about the error.
See “Using the Setup utility” on page 21.
2.
(Trained service technician only) Replace
the system-board assembly - See
“Removing the system-board assembly” on
page 97 and “Installing the system-board
assembly” on page 98.
SAS storage drive
error
A storage drive has failed.
Run the SAS Attached Disk diagnostic test. If
the drives passes diagnostics but continues to
have a problem, replace the storage drive with
a new one. See “Dynamic system analysis
diagnostic programs and messages” on page
189.
186
BladeCenter HS22 Type 7870, 1936, and 1911: Problem Determination and Service Guide
Содержание 1911
Страница 1: ...BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 2: ......
Страница 3: ...BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 14: ...xii BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 20: ...6 BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 34: ...20 BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 248: ...234 BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 252: ...238 BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 260: ...246 BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 265: ...W Web site ServerGuide 31 Windows IPMI device driver 38 WOL disable switch 17 wrong characters 170 Index 251 ...
Страница 266: ...252 BladeCenter HS22 Type 7870 1936 and 1911 Problem Determination and Service Guide ...
Страница 267: ......
Страница 268: ... Part Number 90Y5614 Printed in USA 1P P N 90Y5614 ...