• The VariMax50 NG is part of a new range of control units that, with the necessary  

additional functions, are suitable for the optimum control of rotary heat exchangers.  

The series comes in two sizes, the VariMax25 NG and VariMax50 NG.  

Both the control units operate 3-phase stepper motors.  

The control units have a 0-10 V input signal. 

• The VariMax50 NG is intended for rotors up to 2500 mm with a max rotor speed of  

12 rpm. If the rotor requires a higher rotor speed, rotor diameter should be reduced. 

• The VariMax50 NG has internal Modbus functions. 

For more information, see the manual on our website, www.ibccontrol.se

• The VariMax50 NG has an integrated input signal offset, which means rotor efficiency is 

proportional to the input signal.

• The VariMax50 NG threshold is set at 0.1 V (hysteresis 0.13 - 0.07 V). If the input signal 

drops below this value, the rotor will stop.

• 

The VariMax50 NG has an internal rotation monitor. The rotation monitor is patent 

pending.  

 

This is activated when the DIP switch for the “External rotation monitor” is in the OFF 

position.  

 

The internal rotation monitor performs measurements at different times, depending on 

whether the speed of the motor is above or below 37 rpm. 

 

At a motor speed above 37 rpm, the measurement begins when the speed is stable,  

normally starting after about 30 seconds, after which measurements are carried out  

continually. The yellow “Rotation” LED flashes after each completed, approved  

measurement. The time between the measurements varies from 22 seconds to nearly two 

minutes. 

 

At a motor speed below 37 rpm, the control unit will increase the speed to 37 rpm at  

two-hour intervals. At start-up, this measurement will start after 10 minutes. 

The speed will remain steady for 2 minutes, while the actual measurement is being  

performed. To verify the measurement, an additional measurement is conducted  

10 minutes later. If both of these measurements are positive, i.e. everything is normal,  

the next measurement will not take place until two hours later. 

This sequence is then repeated with the same time intervals, provided the motor speed is 

below 37 rpm.

DESCRIPTION OF FUNCTIONS

Continued on next page

Содержание VariMax50

Страница 1: ...IBCcontrol NG MANUAL CONTROL UNIT FOR ROTARY HEAT EXCHANGER VariMax50 M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter p h jden Article no F21050305...

Страница 2: ......

Страница 3: ...chnical data control unit 6 Technical data motor 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Reset 9 Connection diagram 10 Connections 10 11 Input sign...

Страница 4: ...cycling When replacing components or when the control unit must be replaced in its entirety please follow the advice below The aim should always be maximum possible recycling of raw materials with min...

Страница 5: ...afety during operation 3 MANUFACTURER S DECLARATION Manufacturer IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Product Control unit for rotary heat exchanger Type designation VariMax50 NG...

Страница 6: ...ated when the DIP switch for the External rotation monitor is in the OFF position The internal rotation monitor performs measurements at different times depending on whether the speed of the motor is...

Страница 7: ...ble and EMC gland to the motor Other cables do not need to be shielded or EMC glands The VariMax50 NG starts automatically following a power failure and resets all alarms upon restarting The VariMax50...

Страница 8: ...A Exact value cannot be obtained with a digital measuring instrument TECHNICAL DATA CONTROL UNIT Max moment 4 Nm Min rpm 1 rpm Max speed rpm 375 rpm Motor temperature mantle max 110 O C Shaft diamete...

Страница 9: ...N Low speed The rotor rotates at the pre set min speed 1 rpm when the DIP switch is set to ON Modbus termination If the control unit is last in the Modbus loop the DIP switch must be in the ON positio...

Страница 10: ...if two consecutive measurements indicate that the rotor is not rotating For more information see Description of functions on page 4 Broken belt Belt slipping Stuck wheel Generates an alarm and trips i...

Страница 11: ...resetting the control unit The control unit is also reset in the event of voltage drop out and closure between terminal 11 and 12 Motor temperature The control unit regulates power and makes sure the...

Страница 12: ...rrent circuit breaker may be connected Motor U V W A VariMax50 NG motor must be used Direction of rotation is changed by switching two of the phases Manual speed A1 A2 Produces set rotation speed on c...

Страница 13: ...nt of alarm The control unit is reset automatically in the event of voltage drop out Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 0 5 A resistive load 30...

Страница 14: ...make sure the DIP switch is set to OFF Checking the cleaning function Switch off the voltage Make sure the Cleaning function DIP switch is set to ON and the input signal is disconnected After switchi...

Страница 15: ...ielded Motor NCY HAR UL CSA 4G0 75 Shielded Input signal 2 0 34 0 5 Does not need shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EM...

Страница 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21050905GB VERSION 1 0 2020 10 01...

Отзывы: