12 V output
(3-11)

Output for 12 V DC. Terminal connection 3 is minus (-),  
terminal connection 11 is plus (+).
Max 50 mA.

External rotation 
monitor
(9-10)

If an external rotation monitor is used, this is connected as shown below.   
White cable connected to terminal 9, brown to terminal 10.
The magnet is installed with south side (S) towards the sensor.
Max. gap 15 mm.

Reset
(11-12)

Remote reset in the event of alarm. 
The control unit is reset automatically in the event of voltage drop-out. 

Alarm relay
(13-14-15

Closes between 14-15 in the event of an alarm or voltage drop-out.
Max 0.5 A resistive load / 30 V AC/DC.

Modbus
(A-B-C)

If Modbus must be used, refer to the separate manual on our website, 
www.ibccontrol.se.

11

Continued from previous page

INPUT SIGNAL/ROTATION SPEED

The input signal is directly proportional to the efficiency of the wheel, which means that input signal and 
rotation speed are as per adjoining diagram.

Input signal - rotation speed

Input signal 0 - 10 V

Rotation speed (%)

Содержание VariMax50

Страница 1: ...IBCcontrol NG MANUAL CONTROL UNIT FOR ROTARY HEAT EXCHANGER VariMax50 M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter p h jden Article no F21050305...

Страница 2: ......

Страница 3: ...chnical data control unit 6 Technical data motor 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Reset 9 Connection diagram 10 Connections 10 11 Input sign...

Страница 4: ...cycling When replacing components or when the control unit must be replaced in its entirety please follow the advice below The aim should always be maximum possible recycling of raw materials with min...

Страница 5: ...afety during operation 3 MANUFACTURER S DECLARATION Manufacturer IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Product Control unit for rotary heat exchanger Type designation VariMax50 NG...

Страница 6: ...ated when the DIP switch for the External rotation monitor is in the OFF position The internal rotation monitor performs measurements at different times depending on whether the speed of the motor is...

Страница 7: ...ble and EMC gland to the motor Other cables do not need to be shielded or EMC glands The VariMax50 NG starts automatically following a power failure and resets all alarms upon restarting The VariMax50...

Страница 8: ...A Exact value cannot be obtained with a digital measuring instrument TECHNICAL DATA CONTROL UNIT Max moment 4 Nm Min rpm 1 rpm Max speed rpm 375 rpm Motor temperature mantle max 110 O C Shaft diamete...

Страница 9: ...N Low speed The rotor rotates at the pre set min speed 1 rpm when the DIP switch is set to ON Modbus termination If the control unit is last in the Modbus loop the DIP switch must be in the ON positio...

Страница 10: ...if two consecutive measurements indicate that the rotor is not rotating For more information see Description of functions on page 4 Broken belt Belt slipping Stuck wheel Generates an alarm and trips i...

Страница 11: ...resetting the control unit The control unit is also reset in the event of voltage drop out and closure between terminal 11 and 12 Motor temperature The control unit regulates power and makes sure the...

Страница 12: ...rrent circuit breaker may be connected Motor U V W A VariMax50 NG motor must be used Direction of rotation is changed by switching two of the phases Manual speed A1 A2 Produces set rotation speed on c...

Страница 13: ...nt of alarm The control unit is reset automatically in the event of voltage drop out Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 0 5 A resistive load 30...

Страница 14: ...make sure the DIP switch is set to OFF Checking the cleaning function Switch off the voltage Make sure the Cleaning function DIP switch is set to ON and the input signal is disconnected After switchi...

Страница 15: ...ielded Motor NCY HAR UL CSA 4G0 75 Shielded Input signal 2 0 34 0 5 Does not need shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EM...

Страница 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21050905GB VERSION 1 0 2020 10 01...

Отзывы: