12
Check that
the control unit is connected as per instructions on page 10.
Connection voltage 1x230-240 V +/-15%, 50/60 Hz.
Check that
the input signal is 0-10 V.
Check that
rotation monitor and cleaning function are connected.
CHECKS BEFORE POWERING UP THE CONTROL UNIT
Check that
the motor rotates in the right direction in relation to the wheel's direction
of rotation.
In the event of a fault, switch two phases to the motor.
Adjustment of max.
speed
Set the “High Speed” DIP switch to the ON position.
Adjust “Max rpm” until the rotor rotates at 10-12 rpm (or as directed by
the rotor manufacturer).
After a test run, make sure the DIP switch is set to OFF.
Checking minimum
speed
Set the “Low Speed” DIP switch to ON.
Check that the wheel starts.
The minimum speed is pre-set.
After a test run, make sure the DIP switch is set to OFF.
Checking the
cleaning function
Switch off the voltage.
Make sure the “Cleaning function” DIP switch is set to ON and the input
signal is disconnected.
After switching on the voltage, the cleaning function starts by the rotor
rotating for 6 seconds with a motor speed of 5 rpm, after which the rotor
stops for 3 seconds.
After this, the actual cleaning function starts, for a random time, between
10 to 20 seconds with the motor at 20 rpm
Checking the
Internal rotation
monitor
External rotation
monitor
The yellow “Rotation” LED will flash following an approved measure-
ment. For more information, see “Description of functions” on page 4.
The yellow “Rotation” LED will flash when the magnet passes the
rotation monitor, regardless of DIP switch position.
Finish by
having the control unit drive the wheel at maximum and minimum
rotation speed and checking that the wheel speed is correct.
PUTTING THE EQUIPMENT INTO OPERATION
Should be done in sequence