12

Check that

the control unit is connected as per instructions on page 10.
Connection voltage 1x230-240 V +/-15%, 50/60 Hz.

Check that

the input signal is 0-10 V.

Check that

rotation monitor and cleaning function are connected.

CHECKS BEFORE POWERING UP THE CONTROL UNIT

Check that

the motor rotates in the right direction in relation to the wheel's direction 
of rotation. 
In the event of a fault, switch two phases to the motor.

Adjustment of max. 
speed

Set the “High Speed” DIP switch to the ON position. 
Adjust “Max rpm” until the rotor rotates at 10-12 rpm (or as directed by 
the rotor manufacturer).  
After a test run, make sure the DIP switch is set to OFF.

Checking minimum 
speed

Set the “Low Speed” DIP switch to ON. 
Check that the wheel starts. 
The minimum speed is pre-set.  
After a test run, make sure the DIP switch is set to OFF.

Checking the  
cleaning function

Switch off the voltage.
Make sure the “Cleaning function” DIP switch is set to ON and the input 
signal is disconnected. 
After switching on the voltage, the cleaning function starts by the rotor 
rotating for 6 seconds with a motor speed of 5 rpm, after which the rotor 
stops for 3 seconds. 
After this, the actual cleaning function starts, for a random time, between 
10 to 20 seconds with the motor at 20 rpm

Checking the 
Internal rotation 
monitor

External rotation 
monitor

The yellow “Rotation” LED will flash following an approved measure-
ment. For more information, see “Description of functions” on page 4.

The yellow “Rotation” LED will flash when the magnet passes the  
rotation monitor, regardless of DIP switch position. 

Finish by

having the control unit drive the wheel at maximum and minimum 
rotation speed and checking that the wheel speed is correct. 

PUTTING THE EQUIPMENT INTO OPERATION

Should be done in sequence

Содержание VariMax50

Страница 1: ...IBCcontrol NG MANUAL CONTROL UNIT FOR ROTARY HEAT EXCHANGER VariMax50 M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter p h jden Article no F21050305...

Страница 2: ......

Страница 3: ...chnical data control unit 6 Technical data motor 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Reset 9 Connection diagram 10 Connections 10 11 Input sign...

Страница 4: ...cycling When replacing components or when the control unit must be replaced in its entirety please follow the advice below The aim should always be maximum possible recycling of raw materials with min...

Страница 5: ...afety during operation 3 MANUFACTURER S DECLARATION Manufacturer IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Product Control unit for rotary heat exchanger Type designation VariMax50 NG...

Страница 6: ...ated when the DIP switch for the External rotation monitor is in the OFF position The internal rotation monitor performs measurements at different times depending on whether the speed of the motor is...

Страница 7: ...ble and EMC gland to the motor Other cables do not need to be shielded or EMC glands The VariMax50 NG starts automatically following a power failure and resets all alarms upon restarting The VariMax50...

Страница 8: ...A Exact value cannot be obtained with a digital measuring instrument TECHNICAL DATA CONTROL UNIT Max moment 4 Nm Min rpm 1 rpm Max speed rpm 375 rpm Motor temperature mantle max 110 O C Shaft diamete...

Страница 9: ...N Low speed The rotor rotates at the pre set min speed 1 rpm when the DIP switch is set to ON Modbus termination If the control unit is last in the Modbus loop the DIP switch must be in the ON positio...

Страница 10: ...if two consecutive measurements indicate that the rotor is not rotating For more information see Description of functions on page 4 Broken belt Belt slipping Stuck wheel Generates an alarm and trips i...

Страница 11: ...resetting the control unit The control unit is also reset in the event of voltage drop out and closure between terminal 11 and 12 Motor temperature The control unit regulates power and makes sure the...

Страница 12: ...rrent circuit breaker may be connected Motor U V W A VariMax50 NG motor must be used Direction of rotation is changed by switching two of the phases Manual speed A1 A2 Produces set rotation speed on c...

Страница 13: ...nt of alarm The control unit is reset automatically in the event of voltage drop out Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 0 5 A resistive load 30...

Страница 14: ...make sure the DIP switch is set to OFF Checking the cleaning function Switch off the voltage Make sure the Cleaning function DIP switch is set to ON and the input signal is disconnected After switchi...

Страница 15: ...ielded Motor NCY HAR UL CSA 4G0 75 Shielded Input signal 2 0 34 0 5 Does not need shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EM...

Страница 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21050905GB VERSION 1 0 2020 10 01...

Отзывы: