Manual
Issue 1.5
71
Configuration
Input
Select the input signal.
Update interval
If the spectrum is required in another update time than 200 ms, you can set here as a
default which time interval should be used.
Harmonics values
Select whether to measure relative or absolute harmonics/interharmonics.
Enable phase calculation
The corresponding phases for the harmonic values are also calculated.
Interference factor
Different calculation types can be selected for an interference factor.
Type:
TIF
(acc. to IEEE Std. 519)
:
Describes the effects of harmonic voltages or cur-
rents on communication systems near transmission lines.
THFF:
European version of the TIF defined by the CCITT (Comité Consultatif In-
ternational Téléphonique et Télégraphique), now ITU-T, in 1978.
Linear
: General calculation formula with harmonic values without squaring.
Square
: General calculation formula with squared harmonics
Psophometry up to 50th harmonic can be mapped using the type
square
and the
normalization
Hn
.
Since ibaPDA supports only one weighting factor per harmonic, the factors have
to be multiplied first for psophometry and specified as total weighting factor per
harmonic.
Содержание ibaPQU-S
Страница 6: ...Manual ibaPQU S 6 Issue 1 5 14 Index 125 15 Certificate 126 16 Support and contact 127...
Страница 23: ...Manual Issue 1 5 23...
Страница 90: ...Manual ibaPQU S 90 Issue 1 5 Distance between two ibaPQU S systems Dimensions in mm...
Страница 91: ...Manual Issue 1 5 91 ibaPQU S and backplane Dimensions in mm...
Страница 92: ...Manual ibaPQU S 92 Issue 1 5 Dimensions of ibaPADU S B1S with modules dimensions in mm...
Страница 106: ...Manual ibaPQU S 106 Issue 1 5 12 3 2 3 Dimensions Dimensions in mm...
Страница 124: ...Manual ibaPQU S 124 Issue 1 5 Example of 1 phase measuring with a Rogowski coil or a current clamp...
Страница 126: ...Manual ibaPQU S 126 Issue 1 5 15 Certificate...