Under “Measured values” select whether voltages only, currents only or voltages and
currents are measured.
12.
To perform measurements according to a defined st
andard, click the link “Click to
configure standards...” and select the desired standard.
By selecting the standard, all characteristic values required for measurement and
calculation according to the standard are determined automatically. The selection
causes the corresponding submodules comprising the different power quality char-
acteristic values to be added to the “Grid” module.
13.
If the standard “EN50160” is selected, 7 submodules are displayed which determine
all characteristic values required according to DIN EN 50160 (power frequency, sup-
ply voltage variation, flicker severity, supply voltage unbalance, harmonic voltage,
mains signalling voltage, voltage events).