Power Supply and Stop Circuit (Example) 

In the diagram below shows a circuit related to RCON drive source cutoff. For RCON, motor power is 
supplied from the gateway unit, but the circuit related to the drive-source cutoff is on the driver unit side. 

  Each driver unit possesses an interface (Drive source cutoff connector: MPI/MPO) available for external 

drive source cutoff prepared for each axis. 

  Each driver unit possesses a drive source cutoff circuit by semiconductor prepared for each axis. The 

motor power should be cut off by STOP Signal. The drive source cutoff circuit by semiconductor 
possesses features to detect the overcurrent and to limit the in-rush current. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note 1  RCON-GW  :  If nothing is connected to the SIO connector, S1 and S2 will be short-circuited in the controller. 
 

RCON-GWG :  If nothing is connected to the SIO connector, S1 and S2 will not be short-circuited in the controller.   

To short-circuit, connect the supplied dummy plug DP-5 to the SIO connector. 

Note 

 When externally shutting off the motor drive source to comply with the safety category or the like, connect a contact 

such as a relay to the wiring between the MPI* and MPO* terminals. 

 

 The rating of the STOP-signal to be turned ON/OFF with the contact CR1 is 24 VDC / 10 mA or less. 

 

 The CR1 coil current must be 0.1 A or less. 

 

 When supplying power by turning ON/OFF 24 VDC, leave 0 V connected and supply/cut off +24 V. 

 

Warning  :  Note that the teaching pendant cannot have a stop for the system side even though it can have a stop for 

all the actuators connected to RCON unit. 

 
 

Current Amperage 

For current amperage, refer to the first step guide for RCON driver unit.. 
 

Item 

Document 

Control 

RCON 24V Driver Unit, Fan Unit, Simple Absolute Unit and Extension Unit First Step Guide 

ME0383 

RCON 200V Power Supply Unit, Driver Unit, Fan Unit, Terminal Unit First Step Guide 

ME0397 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Field Network Wirings and Settings 

The field network connector is allocated on the top of the gateway unit. Refer to “Names for Each Part”. 

 

1. CC-Link (RCON-GW/GWG-CC) 

Refer to the instruction manuals for each field network master unit and mounted PLC for the details. 

 
 
 
 
 
 

 

Connector Name

CC-Link Connector 

Remarks 

Cable Side 

MSTB2.5/5-STF-5.08 AU 
(Manufactured by PHOENIX CONTACT) 

Enclosed in 
standard package

Controller Side 

MSTB2.5/5-GF-5.08 AU 
(Manufactured by PHOENIX CONTACT) 

 

 

Pin

No.

Signal Name 

(Color)

Description 

Applicable cable 

diameter

1 DA (BL)

Communication Line A

Dedicated cable 
for CC-Link 

2 DB (WT) 

Communication Line B 

3 DG (YW)

Digital Ground

4

SLD 

Connect the shield of the shielded cable 

(Connected inside to 5-pin FG and control power 
supply connector 1-pin FG)

5

FG 

Frame Ground 

(Connected inside to 4-pin SLD and control power 
supply connector 1-pin FG)

 
 
 
 
 
 
 
 
 
 
 

 

2. CC-Link IE Field (RCON-GW/GWG-CIE) 

Refer to the instruction manuals for each field network master unit and mounted PLC for the details. 

 
 
 

 

Connector Name

CC-Link IE Field Connector 

Remarks 

Cable Side 

Ethernet ANSI/TIA/EIA-568-B Category 5e 
and above 8P8C modular plug equipped 
with shield (RJ45)

Please prepare 
separately 

Controller Side 

Ethernet ANSI/TIA/EIA-568-B Category 5e 
and above 8P8C modular Jack equipped 
with shield (RJ45)

 

 

Pin 

No.

Signal Name

Description 

Applicable cable 

diameter

1 TP0+ 

Data 0+ 

It is recommended 
to prepare a 
straight STP cable 
in Category 5e or 
above for the 
Ethernet cable. 

2 TP0- 

Data 0- 

3 TP1+ 

Data 1+ 

4 TP2+ 

Data 2+ 

5 TP2- 

Data 2- 

6 TP1- 

Data 1- 

7 TP3+ 

Data 3+ 

8 TP3- 

Data 3- 

 
 
 
 
 
 
 
 
 
 
 
 

3. DeviceNet (RCON-GW/GWG-DV) 

Refer to the instruction manuals for each field network master unit and mounted PLC for the details. 

 
 
 
 
 
 
 
 

Connector Name 

DeviceNet Connector 

Remarks 

Cable Side 

MSTB2.5/5-STF-5.08 AU M 
(Manufactured by PHOENIX CONTACT) 

Enclosed in 
standard package

Controller Side 

MSTB2.5/5-GF-5.08 AU 
(Manufactured by PHOENIX CONTACT) 

 

 

Pin 

No. 

Signal Name 

(Color) 

Description 

Applicable cable 

diameter 

1  V- (BK) 

Power Supply Cable Negative Side 

Dedicated cable 
for DeviceNet 

2  CAN L (BL)  Communication Data Low Side 
3  - 

Digital Ground 

4  CAN H (WT)  Communication Data High Side 
5  V+ (RD) 

Power Supply Cable Positive Side 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

4. EtherCAT (RCON-GW/GWG-EC) 

Refer to the instruction manuals for each field network master unit and mounted PLC for the details. 

 
 
 
 

Connector Name 

EtherCAT Connector

Remarks

Cable Side 

Ethernet ANSI/TIA/EIA-568-B Category 5 
and above 8P8C modular plug equipped 
with shield (RJ45)

Please prepare 
separately 

Controller Side 

Ethernet ANSI/TIA/EIA-568-B Category 5 
and above 8P8C modular Jack equipped 
with shield (RJ45)

 

 

Pin 

No. 

Signal Name 

Description 

Applicable cable 

diameter 

1  TD+ 

Data  

It is recommended 
to prepare a 
straight STP cable 
in Category 5 or 
above for the 
Ethernet cable. 

2  TD- 

Data sending- 

3  RD+ 

Data re 

4  - 

Disconnected 

5  - 

Disconnected 

6  RD- 

Data receiving- 

7  - 

Disconnected 

8  - 

Disconnected 

 
 
 
 
 
 
 
 
 
 
 
 
 

Top View of 

Connector on 

Controller side 

L.ER
 
 
 
LINK

L.ER
 
 
 
LINK

5

4

3

2

1

Top View of 

Connector on 

Controller side

Shield

BL (CAN L)

RD (V+)

WT (CAN H)

BK (V-)

Slave Devices

RCON-DeviceNet Type

V+

Drain

(Shield)

CAN_H

CAN_L

V-

RD

WT

BL

BK

RD

WT

BL

BK

V+

Drain

(Shield)

CAN_H

CAN_L

Grounding resistance at 100

Ω

 or less 

(Class D grounding)

V+

Drain

(Shield)

CAN_H

CAN_L

V-

RD

WT

BL

BK

Communication power needs to be 
supplied by an external device.

Terminal Resistance is required 
to be mounted on the terminal.

V-

Terminal Resistance
121

Ω

Master Unit

Terminal Resistance

121

Ω

24V 
Power Supply

5

4

3

2

1

Top View of 

Connector on 

Controller side

WT (DB)

BL (DA)

Shield (SLD)

YW (DG)

Slave Devices

RCON-
CC-Link 
Type

SLD and FG are internally connected.

Terminal Resistance is required 
to be mounted on the terminal.

The terminal resistor differs depending on the type 
of the dedicated cable for CC-Link.
• Cable FANC-SBH···130

Ω

1/2W

                                  (High Performance Cable 
                                   dedicated for CC-Link)
• Cable FANC-SB······110

Ω

1/2W

                                  (CC-Link Dedicated Cable)

Master Unit

Terminal 
Resistance

Terminal

Resistance

Grounding resistance at 100

Ω

 or less 

(Class D grounding)

Master Unit 

Slave Devices 

RCON EtherCAT Type 

Ethernet Straight Cable    Category 5 or more 
Double shielded cable braided with aluminum foil recommended

(Note) Terminal resistance is not required 

Master Unit

Slave Devices

RCON CC-Link IE Field Type

Ethernet Straight Cable    Category 5e or more 
Double shielded cable braided with aluminum foil recommended

(Note) Terminal resistance is not required 

There is no 
distinction of IN/OUT 
on the connector. 

Gateway unit

Driver unit

Driver unit

SIO connector

System I/O

connector

Motor

power

connector

Control

power

connector

Note 1

Control

power

24V

Stop

reset

switch

Stop

switch

Teaching pendant

Stop switch

Drive-source

cutoff

connector

Drive-source

cutoff

connector

Mo

to

po

w

er

Mo

to

po

w

er

Mo

to

po

w

er

Mo

to

po

w

er

Hi

gh-

side

 prot

ec

tion 

cir

cuit

Hi

gh-

side

 prot

ec

tion 

cir

cuit

Hi

gh-

side

 prot

ec

tion 

cir

cuit

Hi

gh-

side

 prot

ec

tion 

cir

cuit

24V

dedicated

for stop

circuit

Top View of 

Connector on 

Controller side 


 
 
 


 
 
 

OUT

 

IN

 

Содержание RCON-GW

Страница 1: ...cations of Power Supply Item Specification Power Input Voltage Range 24V DC 10 Supply Current Refer to Current Amperage in RCON Driver Unit First Step Guide ME0383 Current Amperage Refer to Current Amperage in RCON Driver Unit First Step Guide ME0383 In Rush Current Refer to Current Amperage in RCON Driver Unit First Step Guide ME0383 Instantaneous Power Outage Endurance By 24V power supply Protec...

Страница 2: ...the following environment Location where the ambient temperature is out of the range between 0 and 55 C with fan or 0 and 40 C with no fan Location where condensation occurs due to abrupt temperature changes Location where relative humidity exceeds 85 RH Location exposed to corrosive gases or combustible gases Location exposed to significant amount of dust salt or iron powder Location subject to d...

Страница 3: ...thernet cable 2 TP0 Data 0 3 TP1 Data 1 4 TP2 Data 2 5 TP2 Data 2 6 TP1 Data 1 7 TP3 Data 3 8 TP3 Data 3 3 DeviceNet RCON GW GWG DV Refer to the instruction manuals for each field network master unit and mounted PLC for the details Connector Name DeviceNet Connector Remarks Cable Side MSTB2 5 5 STF 5 08 AU M Manufactured by PHOENIX CONTACT Enclosed in standard package Controller Side MSTB2 5 5 GF ...

Страница 4: ...ting Confirmed STOP Signal input driver unit drive source being cut off OFF No STOP Signal input confirmed MODE GN Illuminating In AUTO automatic operation Mode OFF In MANU manual operation Mode C ERR OR Illuminating Error occurred in field network OFF Field network operating in normal conditions STATUS 0 Differs depending on field network Refer to Field Network Communication Conditions from 1 to ...

Страница 5: ...l Display Color Status Explanation STATUS 0 MS GN Illuminating Initialization completed Flashing Initialization completed there is a diagnosis event RD Illuminating Exception error GN RD OFF Not initialized STATUS 1 NS GN Illuminating Online data exchange Flashing Online cleared RD Illuminating Parameter error Flashing Configuration error GN RD OFF Offline 7 PROFINET IO RCON GW GWG PRT Name Panel ...

Отзывы: