The emergency light standard IEC 60598-2-22 states that emergency lights must
be classified in accordance with their design and operation. This classification must
be marked on the luminaire and completed at the installation stage.
X
1
a) The first field contains a single character that indicates the luminaire type:
X – self-contained (luminaire-specific battery)
Z – connected to central battery
b) The second field indicates the luminaire’s operating mode with a single digit:
0 - non-maintained emergency luminaire
1 - maintained emergency luminaire
2 - combined non-maintained luminaire
3 - combined maintained luminaire
4 - compound non-maintained luminaire
5 - compound maintained luminaire
6 - satellite emergency luminaire
c) The third field is filled in connection with installation, when the accessories are known:
A - including test device
B - including remote rest mode
C - including inhibiting mode
D - high-risk task-area luminaire
E - with non-replacable lamp(s) and/or battery
d) In the fourth field, the markings indicate the minimum duration of the emergency mode
for self-contained luminaires, expressed in minutes.
10 - operating time of 10 min.
60 - operating time of 1 hour