AUTO TUNING MODE : 

To enter in this mode, Press and hold SHIFT key for minimum 3 sec. 

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

DEFAULT

DESCRIPTION

This  function  will  be  executed  only  if  selected  control  action  is  PID  & Auto  tune  is 
Enable.
The  Auto-tuning  function  can  be  initiated  by  setting  this  parameter  to  YES.  The 
decimal  of  LSB  flashes  till  auto  tuning  function  is  in  progress.  During Auto-tuning, 
The controller learns the process characteristics by itself & calculates required P, I 
& D values.
User can cancel or abort this feature by setting this parameter to NO.

AUTO

TUNING

MODE

NO

USER GUIDE 

: -

ON-OFF ACTION :

 In this mode, Output (Relay/SSR) remains ON till actual temperature reaches to the set point value. On 

reaching to SP, Output turns OFF & remains OFF till actual temperature drops down (in Heat Logic) or raises (in Cool Logic) 
equal to hysterisis set by user. (As shown in Fig. 3.1 & 3.2)

AUTO TUNING MODE :

 In this mode, Controller learns the  process characteristics by itself and calculates the required P,I & 

D  values. It can be performed at any time after power ON but, it is best to start it when the process is at Ambient temperature 
in order to minimize overshoot & undershoot. Auto tuning is applied in case of : 
(1) Initial set up for a new process. 
(2) Substantial change in SP from previous auto tuning value. 
(3) Control accuracy is not satisfactory. 
If the control performance by using auto-tuning is still unsatisfactory, User can apply further adjustments of P,I & D values as 
shown in Table:3 below.

Fig: 3.1

HEAT LOGIC / ON-OFF

TIME

0

TEMP ( C)

HYSTERISIS

SP

ON

ON

ON

AMB

O/P

OFF

OFF

Fig: 3.2

TIME

COOL LOGIC / ON OFF

O/P

O/P

0

TEMP ( C)

AMB

HYSTERISIS

ON

ON

ON

SP

OFF

OFF

Proportional Band

Integral Time

Derivative Time

Slow Response
Over Shoot or Oscillations
Slow Response
Instability or Oscillation
Slow Response or Oscillation
High Over Shoot

Decrease PB
Increase  PB
Decrease  Int
Increase  Int
Decrease  Dt
Increase  Dt

Adjust

Symptom

Solution

Table: 3

NC

: Normally Close terminal of relay

NO

: Normally  Open terminal of relay   

OP1

: Output 1 

OP2

: Output 2

C.A. 

: Control Action   

CJC 

: Cold junction compensation 

CM

: Common terminal of relay    

LWC

: Lead wire (Length)-  

              compensation

SP1

: Set Point Value (set temp.) 

PV

: Process Value (actual Tmp.)  

SSR

: Solid State Relay

T/C

: Thermocouple

ABBREVIATION :

9

OIM AI-7X82 V2.0 Page 9 of 9

413, New Sonal Link Service Industrial Premises Co-op Society Ltd,
Building No.2, Link Road, Malad (W), Mumbai - 400064. 
Tel: 022-66939916/17/18; 
E-mail : [email protected] 
Website : www.itherm.co.in  

Mfgd  by:  Innovative  Instruments  &  Controls  LLP

i

Содержание AI-7482

Страница 1: ...bon dust salt air direct sunlight or radiant heat v Ambient temperature and relative humidity surrounding the controller must not exceed the maximum specified limit for proper operation of the controller v The controller in its installed state must be protected against excessive electrostatic or electromagnetic interferences Ventilation holes provided on the chassis of the instrument are meant for...

Страница 2: ...782 AI 7982 FRONT PANEL LAYOUT AI 7882 AI 7682 Glows when OP1 is ON flashes when delay time dly1 is in operation if selected mode is ON OFF Glows when OP2 is ON flashes when alarm condition persists even after acknowledged OR delay time dly2 is in operation selected mode is ON OFF Glows when Soak mode is selected flashes when Soak timer is in operation along with UP key 4 To scroll the parameter t...

Страница 3: ...upon the error SV PV Value of this parameter is automatically set by Auto tune function o 5 0 C LOWER DISPLAY UPPER DISPLAY PARA METER RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters OUTPUT OFF 1 to10 This parameter will be prompted only if selected control action is PID With this parameter ...

Страница 4: ...ered at every power ON This parameter will be prompted only if selected control mode for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously ON at the end of Soak time till User starts the next cycle This parameter defines the permissible deviation of PV f...

Страница 5: ...ID User can select between PID or ON OFF action algorithm to be adopted for output HEAT CONTROL LOGIC FOR O P 1 User can select heating logic in which OP1 will remain ON till PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD or RTD 1 and is used for B...

Страница 6: ...list OUTPUT 2 CONTROL 15 0 This parameter will appear only if Control logic is Heat Cool OP2 will be OFF at Ambient OP2C value irrespective of output 2 mode Auxiliary Toggle OUTPUT 2 FUNCTION This parameter allows the user to select output 2 as an Auxiliary control For options refer Table 3 This parameter allows the user to select output 2 as an Alarm control For options refer Table 4 This paramet...

Страница 7: ...der alarm conditions used to trip the process in alarm conditions ALARM INHIBIT If this parameter is set as YES Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up NO ALARM ACK AUTO Once the Alarm is activated User has following three options to de activate it When PV falls within the programmed...

Страница 8: ... only after pressing START key for 3 sec PV SV for any of the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress TIMER START MODE MOD 2 In this Mode Timer will start only after pressing START key for 3 sec PV SV for any of the following conditions 1 At every Power ON 2 Completion of current soak time cycle After executin...

Страница 9: ... undershoot Auto tuning is applied in case of 1 Initial set up for a new process 2 Substantial change in SP from previous auto tuning value 3 Control accuracy is not satisfactory If the control performance by using auto tuning is still unsatisfactory User can apply further adjustments of P I D values as shown in Table 3 below Fig 3 1 HEAT LOGIC ON OFF TIME 0 TEMP C HYSTERISIS SP ON ON ON AMB O P O...

Отзывы: