background image

8

4.3 NGRS-XX RESISTOR SENSOR

The NGRS-XX resistor sensor must be selected from those available from I-GARD and must be rated for the system 
voltage in which it will be installed.

4.3.1 Location

The NGRS-XX resistor sensor should be mounted near the system transformer, along with the ZSCS and the NGR.

4.3.2 Mounting

The overall dimensions of the NGRS-XX resistor sensor are 89 mm x 65 mm x 71 mm (for the low voltage units). 
A metal mounting bracket extends from one side of the housing. The bracket has two 6 mm mounting holes in it 
through which bolts or self threading screws can be used to mount the NGRS-XX resistor sensor to a flat surface. 
Refer to Figure 4 for higher voltage NGRS resistor sensors.

4.3.3 CONNECTIONS

The neutral terminal of the NGRS-XX resistor sensor must be connected to the ungrounded end of the NGR. This is 
the same connection point as is connected to the system transformer’s neutral. Refer to Figure 2.

The R terminal of the NGRS-XX resistor sensor must be connected to terminal 45 of the SIGMA-MD monitor relay as 
shown in Figure 2. The G terminal of the NGRS-XX resistor sensor should be connected to a suitable ground point. 
This grounding point should be separate from the ground path from the NGR so that the ground path from the NGR 
is monitored as well as the NGR itself.

4.4 CONFIGURATION OF SIGMA-MD MONITOR RELAY AND NGR

The SIGMA-MD monitor relay has settings for the let-through current, ground fault trip current level and ground 
fault time delay. These settings may be specified in the installation requirements. However, the let-through current 
and ground fault trip current level are, in part, dependent on conditions that can only be determined at the time of 
installation or if and when there are changes to the operating environment.

One of the operating conditions that impact the relay settings is the amount of leakage or charging current in 
the system. This may vary from one installation to another or, as noted above, when there are changes to the 
operating environment.

As the let-through current measured by the zero sequence current sensor will be the vector sum of any leakage 
currents or charging currents normally in the system and any ground fault currents that may be present, it is 
important that the leakage currents or charging currents normally in the system be taken into consideration 
when setting the relay’s ground fault trip points. Failure to take the leakage currents or charging currents into 
consideration may result in false tripping due to the low let-through current settings.

The ground fault trip current level is set as a percentage of the let-through current through the NGR. The ground 
fault trip current level setting available are: 50 %, 40%, 30%, 25%, 20%, 15%, 10% and 5%.

The SIGMA-MD monitor relay has sixteen settings for the let-through current, ranging from 50 A to 800 A with an 
I-GARD TxA type ZSCS.

Содержание SIGMA-MD

Страница 1: ...C EG42EM Instruction Manual December 2018 Previously C 455EM GROUND FAULT RELAY NEUTRAL GROUNDING RESISTOR SIGMA MD...

Страница 2: ...s 10 6 1 Start Up and Reset Indications 10 6 2 Power on Led Green 11 6 3 Ground Fault Led Red 11 6 4 NGR Fault Led Red 11 6 5 Zone Ground Led Red 12 7 Self Test 12 8 Relay Settings 13 8 1 Trip Relay O...

Страница 3: ...omer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in...

Страница 4: ...present Hazard of Electrical Shock Burn or Explosion All installation servicing and testing referred to in this manual must be performed by qualified personnel All power should be disconnected prior...

Страница 5: ...minal value When the ZSCS current is below 1 of the NGR let through current setting the SIGMA MD monitor relay simply monitors the NGR resistance for continuity i e whether the NGR is open or presents...

Страница 6: ...fast response is necessary as failure of the NGR implies that there is limited ground fault protection on the system It also ensures fast tripping when a transformer is energized and the resistor is...

Страница 7: ...necting the NGRS from the SIGMA MD monitor relay the R terminal of the NGRS should be disconnected BEFORE the Ground connection is removed from the G terminal of the SIGMA MD monitor relay The procedu...

Страница 8: ...e trip relay terminals the auxiliary fault relay terminals the external reset test and the G F meter terminals If door panel mounted or remote test and or reset controls are required connect momentary...

Страница 9: ...MD MONITOR RELAY AND NGR The SIGMA MD monitor relay has settings for the let through current ground fault trip current level and ground fault time delay These settings may be specified in the installa...

Страница 10: ...r if the SIGMA MD processor fails this normally closed relay will open The contacts will close when the power LED turns on and remain closed as long as the relay is operating correctly All relays are...

Страница 11: ...et flashing The trip relay auxiliary fault relays and associated LED will remain as such indefinitely regardless of whether a fault is present on the system and until the conditions which caused the t...

Страница 12: ...l be ON when the SIGMA MD monitor relay has detected and qualified a ground fault The RED GND FAULT LED will remain ON until the SIGMA MD monitor relay is manually reset even if the NGR fault conditio...

Страница 13: ...GMA MD monitor relay and no voltage applied to system transformer s primary winding Alternatively the system transformer s primary winding may be powered with the system transformer secondary isolated...

Страница 14: ...en control voltage is applied to the SIGMA MD monitor relay and the system is operating normally The trip relay is energized trip when the measured values of the ground fault current or NGR resistance...

Страница 15: ...A MD monitor relay will resume monitoring of the system and if a fault remains on the system will detect the fault and will re trip de energizing the trip relay 8 2 TRIP MEMORY SETTING The SIGMA MD mo...

Страница 16: ...ble and not higher than 20 when complying with this CSA Mine Safety Standard 8 5 SYSTEM FREQUENCY The SIGMA MD monitor relay has two settings for selecting the AC frequency of the system it monitoring...

Страница 17: ...is Idle Not Tripped Trip Relay is not energized Aux Fault Relays are not energized DOWN SIGMA MD Relay is Tripped Trip Relay is energized Aux Fault Relays are energized MODE DIP SWITCH SETTING Table 1...

Страница 18: ...U U D 1550 D U U U U 1650 U D D D D 1750 U D D D U 1850 U D D U D 1950 U D D U U 2050 U D U D D 2150 U D U D U 2250 U D U U D 2350 U D U U U 2450 U U D D D 2550 U U D D U 2650 U U D U D 2750 U U D U U...

Страница 19: ...y U UP D DOWN Table 4 Ground Fault Trip Current Level Settings SYSTEM FREQUENCY 60 50 Hz DIP SWITCH SETTING SYSTEM FREQUENCY 50 Hz UP SYSTEM FREQUENCY 60 Hz DOWN DIP switch 11 right hand array U UP D...

Страница 20: ...CS 550 U D U D I GARD TxA Type ZSCS 600 U D U U I GARD TxA Type ZSCS 650 U U D D I GARD TxA Type ZSCS 700 U U D U I GARD TxA Type ZSCS 750 U U U D I GARD TxA Type ZSCS 800 U U U U I GARD TxA Type ZSCS...

Страница 21: ...restored after a loss of control power the trip relay and auxiliary fault relays are returned to the state these relays had prior to the loss of control power The state of the trip relay and auxiliary...

Страница 22: ...s open or presents some resistance Trip Time Less than 60 seconds per CAN CSA M421 00 Typically 3 5 seconds 0 100 msec Up to 10 seconds under certain conditions Accuracy NGR Trip Resistance limits in...

Страница 23: ...the conductor on terminal G of the NGRS XX resistor sensor from ground and ensure the conductor is insulated 4 Disconnected the conductors between the X1 and X2 terminals of the TxA type ZSCS and the...

Страница 24: ...in less than 1s if ground fault current exceeds 20 of the prospective ground fault current 3 6 2 Neutral Grounding Devices A neutral grounding device shall be a continuously rated except when ground f...

Страница 25: ...24 Figure 2 Sigma MD Monitor Relay Detail A Typical NGRS Sensing Resistor Ngrs 6 Dual Voltage Model Shown Figure 3 Low Voltage NGRS Resistor Sensor...

Страница 26: ...25 Figure 5 NGRS 50 Figure 4 NGRS 25...

Страница 27: ...26 Figure 6 High Voltage NGRS Resistor Sensors...

Страница 28: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 support i gard com...

Отзывы: