background image

6

The ground fault trip time setting defines the length of time a ground fault must persists before a fault is qualified 
and reported by the relay by operating the ground fault output relay and the main trip relay. This setting can also 
be used to delay the indication by the SIGMA-MD monitor relay of a ground fault. The ground fault trip time is DIP 
switch selectable from its minimum setting of 40-to-60 milliseconds to 3.15 seconds.

DIP switches on the SIGMA-MD monitor relay must be set for the required ground fault time delay and ground fault 
trip current level.

Refer to TABLE 3 for DIP switch settings for the GROUND FAULT TRIP TIME DELAY. Refer to TABLE 4 for DIP switch 
settings for GROUND FAULT CURRENT LEVEL.

4. INSTALLATION INSTRUCTIONS

The G terminal of the SIGMA-MD monitor relay should be connected 
(bonded) to ground as described BEFORE connecting the R terminal 

of the NGRS-XX resistor sensor to the appropriate terminal

on the SIGMA-MD monitor relay. Similarly, when disconnecting the 

NGRS from the SIGMA-MD monitor relay, the R terminal of the NGRS 

should be disconnected BEFORE the Ground connection is

removed from the G terminal of the SIGMA-MD monitor relay.

The procedure described above provides a discharge path for static

electricity which could damage the SIGMA-MD monitor relay.

DANGER

4.1 THE SIGMA-MD MONITOR RELAY

The SIGMA-MD monitor relay detects ground faults by measuring the current through the NGR. The relay compares 
the measured values against the field settings of the relay and provides relay outputs and LED indications when an 
abnormal condition is detected. 

4.1.1 Location

The SIGMA-MD monitor relay should be located as close as possible to the system’s isolating device, circuit breaker 
or contactor.

4.1.2 Mounting

Mount the SIGMA-MD monitor relay horizontally using 35 mm DIN rail bolted or firmly fixed to flat surface. Allow 
at least 20 mm of rail to extend beyond each end of the relay. Secure the relay to the DIN rail ensuring the release 
latches at the bottom of the relay engage the rail. If the relay is to be mounted in any other position take appropriate 
steps to prevent the relay from becoming disengaged from the DIN rail.

Содержание SIGMA-MD

Страница 1: ...C EG42EM Instruction Manual December 2018 Previously C 455EM GROUND FAULT RELAY NEUTRAL GROUNDING RESISTOR SIGMA MD...

Страница 2: ...s 10 6 1 Start Up and Reset Indications 10 6 2 Power on Led Green 11 6 3 Ground Fault Led Red 11 6 4 NGR Fault Led Red 11 6 5 Zone Ground Led Red 12 7 Self Test 12 8 Relay Settings 13 8 1 Trip Relay O...

Страница 3: ...omer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in...

Страница 4: ...present Hazard of Electrical Shock Burn or Explosion All installation servicing and testing referred to in this manual must be performed by qualified personnel All power should be disconnected prior...

Страница 5: ...minal value When the ZSCS current is below 1 of the NGR let through current setting the SIGMA MD monitor relay simply monitors the NGR resistance for continuity i e whether the NGR is open or presents...

Страница 6: ...fast response is necessary as failure of the NGR implies that there is limited ground fault protection on the system It also ensures fast tripping when a transformer is energized and the resistor is...

Страница 7: ...necting the NGRS from the SIGMA MD monitor relay the R terminal of the NGRS should be disconnected BEFORE the Ground connection is removed from the G terminal of the SIGMA MD monitor relay The procedu...

Страница 8: ...e trip relay terminals the auxiliary fault relay terminals the external reset test and the G F meter terminals If door panel mounted or remote test and or reset controls are required connect momentary...

Страница 9: ...MD MONITOR RELAY AND NGR The SIGMA MD monitor relay has settings for the let through current ground fault trip current level and ground fault time delay These settings may be specified in the installa...

Страница 10: ...r if the SIGMA MD processor fails this normally closed relay will open The contacts will close when the power LED turns on and remain closed as long as the relay is operating correctly All relays are...

Страница 11: ...et flashing The trip relay auxiliary fault relays and associated LED will remain as such indefinitely regardless of whether a fault is present on the system and until the conditions which caused the t...

Страница 12: ...l be ON when the SIGMA MD monitor relay has detected and qualified a ground fault The RED GND FAULT LED will remain ON until the SIGMA MD monitor relay is manually reset even if the NGR fault conditio...

Страница 13: ...GMA MD monitor relay and no voltage applied to system transformer s primary winding Alternatively the system transformer s primary winding may be powered with the system transformer secondary isolated...

Страница 14: ...en control voltage is applied to the SIGMA MD monitor relay and the system is operating normally The trip relay is energized trip when the measured values of the ground fault current or NGR resistance...

Страница 15: ...A MD monitor relay will resume monitoring of the system and if a fault remains on the system will detect the fault and will re trip de energizing the trip relay 8 2 TRIP MEMORY SETTING The SIGMA MD mo...

Страница 16: ...ble and not higher than 20 when complying with this CSA Mine Safety Standard 8 5 SYSTEM FREQUENCY The SIGMA MD monitor relay has two settings for selecting the AC frequency of the system it monitoring...

Страница 17: ...is Idle Not Tripped Trip Relay is not energized Aux Fault Relays are not energized DOWN SIGMA MD Relay is Tripped Trip Relay is energized Aux Fault Relays are energized MODE DIP SWITCH SETTING Table 1...

Страница 18: ...U U D 1550 D U U U U 1650 U D D D D 1750 U D D D U 1850 U D D U D 1950 U D D U U 2050 U D U D D 2150 U D U D U 2250 U D U U D 2350 U D U U U 2450 U U D D D 2550 U U D D U 2650 U U D U D 2750 U U D U U...

Страница 19: ...y U UP D DOWN Table 4 Ground Fault Trip Current Level Settings SYSTEM FREQUENCY 60 50 Hz DIP SWITCH SETTING SYSTEM FREQUENCY 50 Hz UP SYSTEM FREQUENCY 60 Hz DOWN DIP switch 11 right hand array U UP D...

Страница 20: ...CS 550 U D U D I GARD TxA Type ZSCS 600 U D U U I GARD TxA Type ZSCS 650 U U D D I GARD TxA Type ZSCS 700 U U D U I GARD TxA Type ZSCS 750 U U U D I GARD TxA Type ZSCS 800 U U U U I GARD TxA Type ZSCS...

Страница 21: ...restored after a loss of control power the trip relay and auxiliary fault relays are returned to the state these relays had prior to the loss of control power The state of the trip relay and auxiliary...

Страница 22: ...s open or presents some resistance Trip Time Less than 60 seconds per CAN CSA M421 00 Typically 3 5 seconds 0 100 msec Up to 10 seconds under certain conditions Accuracy NGR Trip Resistance limits in...

Страница 23: ...the conductor on terminal G of the NGRS XX resistor sensor from ground and ensure the conductor is insulated 4 Disconnected the conductors between the X1 and X2 terminals of the TxA type ZSCS and the...

Страница 24: ...in less than 1s if ground fault current exceeds 20 of the prospective ground fault current 3 6 2 Neutral Grounding Devices A neutral grounding device shall be a continuously rated except when ground f...

Страница 25: ...24 Figure 2 Sigma MD Monitor Relay Detail A Typical NGRS Sensing Resistor Ngrs 6 Dual Voltage Model Shown Figure 3 Low Voltage NGRS Resistor Sensor...

Страница 26: ...25 Figure 5 NGRS 50 Figure 4 NGRS 25...

Страница 27: ...26 Figure 6 High Voltage NGRS Resistor Sensors...

Страница 28: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 support i gard com...

Отзывы: