I-GARD         Gemini Instruction Manual

6

3

 OPERATION

Figure 5 Gemini Control Panel

Upon energizing the control panel only the green SYSTEM HEALTHY light will turn ON signifying that no ground 
faults are on the system and the 

Gemini

 is receiving control voltage. 

Verify the 

Gemini

 condition by pushing the TEST button and holding for the delay time set on the 

GFR-RM.

 

This causes the 

GFR-RM

 to trip. The green light turns OFF, the red GROUND FAULT light turns ON and the fans 

activate. This confirms that control voltage is available, the 

GFR-RM

 is functioning and the fans are operational. 

Push the RESET button to restore the system to normal operational status. The red GROUND FAULT, RESISTOR 
FAULT and TRIP lights will go OFF and the green SYSTEM HEALTHY light will turn ON, and the fans stop.  
(The meter may indicate a slight leakage). The 

Gemini

 is now ready to monitor the distribution system.

When a ground fault occurs the potential between the system neutral and ground will increase causing the 
meter to display the fault level which may be any value between 0 and 100% of 5A. This current is also being 
monitored by the FAULT CURRENT ammeter. If the fault current magnitude is greater than the pick up setting 
of the 

GFR-RM

 and the duration is greater than the time delay setting on the 

GFR-RM

, the 

GFR-RM 

will trip, 

changing the state of the GROUND FAULT TRIP contacts. The green SYSTEM HEALTHY light turns OFF and  
the red GROUND FAULT and TRIP lights turn ON, and cooling fans activate.

By adjustment of the GFR-RM relay, the ground fault pickup level can be set from 5% to 50% of the 5A  
let-through current. The time delay can be adjusted from 60mS to 3.15s. 

T

his allows the 

Gemini

 settings to be 

adjusted for the unique requirements of each system in order to avoid nuisance tripping.

Both ground fault pickup level and time delay are adjusted using the bank of Dipswitches located on the front 
plate of the 

GFR-RM

 relay, which is located inside the 

Gemini

 enclosure. (Refer to I-Gard Manual IM-GFR-RM) 

for complete details of this relay). 

Содержание IPC GEMINI

Страница 1: ...Instruction Manual C 102 high RESISTANCE GROUNDING SYSTEM Gemini the power to protect...

Страница 2: ...compromising of the resistor integrity the patented twin resistance paths in combination with the integrity monitoring relay form the heart of the Gemini system Limiting any ground fault to predetermi...

Страница 3: ...rounding 9 5 2 Definitions and Applicable Standards 9 6 Additional Information 12 7 Instruction Manuals ibc Table of Figures Figure 1 Close up of Front Panel 3 Figure 2 Wiring Diagram for Gemini 4 Fig...

Страница 4: ...ocate and isolate the fault without interrupting or opening circuit breakers This allows for the uninterrupted operation of process equipment Faults are indicated by front panel lights The TRIP lamp l...

Страница 5: ...or severe personal injury Catalogue Numbers for the Gemini are GS 480 5 for 480V and GS 600 5 for 600V 5A resistor units Please ensure before installation of the unit that the correct version has bee...

Страница 6: ...T G SYSTEM HEALTHY A TRIP INDICATING LIGHTS FAULT CURRENT RESISTOR FAULT GROUND FAULT R A Figure 2 Wiring Diagram for Gemini Figure 3 Outside Dimensions CONTACT OPENS AT 110 C AND CLOSES AT 102 C 301...

Страница 7: ...ified as N 10 on terminal block and the system ground to the point identified as G 11 on terminal block Both the Canadian Electrical Code and the National Electrical Code require a minimum size of 8 A...

Страница 8: ...e potential between the system neutral and ground will increase causing the meter to display the fault level which may be any value between 0 and 100 of 5A This current is also being monitored by the...

Страница 9: ...50 IGMAX 8 UP 9 UP 10 UP CURRENT 5A 1000 1 CT 1 DOWN 2 DOWN 3 DOWN 4 DOWN 5 DOWN 6 DOWN Figure 6 GFR RM Dipswitch 4 MAINTENANCE Gemini is designed and constructed to operate properly with minimal mai...

Страница 10: ...system DANGER Hazard of Electrical Shock Burn or Explosion Qualified personnel must perform testing referred to in this manual All power should be disconnected prior to making any connections or disco...

Страница 11: ...rs cables and rotating machines 2 To reduce mechanical stresses in circuits and apparatus carrying fault currents 3 To reduce electric shock hazards to personnel caused by stray ground fault currents...

Страница 12: ...current rating of the grounding impedance In no case shall the neutral conductor be smaller than No 8 copper or No 6 aluminum or copper clad aluminum c System Neutral Connection The system neutral con...

Страница 13: ...ing of the protective device on the system 4 Neutral grounding devices shall have insulation voltages at least equal to the line to neutral voltage 10 1106 Location of Neutral Grounding Devices and Wa...

Страница 14: ...hrough a resistor at the power source to limit the prospective ground fault current to 25 A or less b A grounding circuit shall originate at the grounded side of the resistor and extend along with the...

Страница 15: ...M SIGMA Resistor Monitoring and Ground Fault Relay C 322 MGFR Ground Fault Relay Manual C 409 DSP OHMNI High Resistance Grounding System Manual C 102 Gemini High Resistance Grounding System Manual C 1...

Страница 16: ...7615 Kimbel St Unit 1 Mississauga Ontario Canada L5S 1A8 Phone 905 673 1553 Toll Free 1 800 737 4787 Fax 905 673 8472 e mail sales i gard com www i gard com the power to protect...

Отзывы: