background image

Gemini Instruction Manual         I-GARD

9

5

 APPENDIX 1

5.1  high-Resistance grounding

Both the Canadian Electrical Code, Part 1, C22.1-98 and the National Electrical Code, NFPA 70 1999, 
approve the use of high-impedance grounding neutral systems up to 1000 V. A.C. where the ground fault 
current is limited to 5 amperes or less. These new changes to the electrical code allow users of the Gemini 
to maintain a ground fault current of 5 amperes or less on their electrical distribution system without shutting 
down because of a single ground fault, thereby avoiding unscheduled down times. Gemini users can locate, 
isolate and repair faulty equipment at convenient time. 

The reason for limiting ground fault current by resistance grounding may be one or more of the following, as 
indicated in IEEE Std. 142-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial 
Power Systems

,

 pp. 25-26. 

 

1 )  To reduce burning and melting effects in faulted electric equipment, such as switchgear, transformers, 

cables, and rotating machines.

 

2 ) To reduce mechanical stresses in circuits and apparatus carrying fault currents.

 

3 )  To reduce electric-shock hazards to personnel caused by stray ground-fault currents in the ground 

return path.

 

4 )  To reduce arc blast or flash hazard to personnel who may have accidentally caused or who happen to 

be in close proximity to the ground fault.

 

5 )  To reduce the momentary line-voltage dip occasioned by the occurrence and clearing of a ground fault.

To secure control of transient over voltages while at the same time avoiding the shutdown of a faulty circuit 
on the occurrence of the first ground fault.

5.2 Definitions and Applicable Standards

Grounding means a permanent and continuous conductive path to the earth with sufficient ampacity to 
carry any fault current liable to be imposed on it, and of a sufficiently low impedance to limit the voltage rise 
above ground and to facilitate the operation of protective devices in the circuit;

Bonding means a low impedance path obtained by permanently joining all non-current-carrying metal  
parts to assure electrical continuity and having the capacity to conduct safely any current likely to be 
imposed on it;

Содержание IPC GEMINI

Страница 1: ...Instruction Manual C 102 high RESISTANCE GROUNDING SYSTEM Gemini the power to protect...

Страница 2: ...compromising of the resistor integrity the patented twin resistance paths in combination with the integrity monitoring relay form the heart of the Gemini system Limiting any ground fault to predetermi...

Страница 3: ...rounding 9 5 2 Definitions and Applicable Standards 9 6 Additional Information 12 7 Instruction Manuals ibc Table of Figures Figure 1 Close up of Front Panel 3 Figure 2 Wiring Diagram for Gemini 4 Fig...

Страница 4: ...ocate and isolate the fault without interrupting or opening circuit breakers This allows for the uninterrupted operation of process equipment Faults are indicated by front panel lights The TRIP lamp l...

Страница 5: ...or severe personal injury Catalogue Numbers for the Gemini are GS 480 5 for 480V and GS 600 5 for 600V 5A resistor units Please ensure before installation of the unit that the correct version has bee...

Страница 6: ...T G SYSTEM HEALTHY A TRIP INDICATING LIGHTS FAULT CURRENT RESISTOR FAULT GROUND FAULT R A Figure 2 Wiring Diagram for Gemini Figure 3 Outside Dimensions CONTACT OPENS AT 110 C AND CLOSES AT 102 C 301...

Страница 7: ...ified as N 10 on terminal block and the system ground to the point identified as G 11 on terminal block Both the Canadian Electrical Code and the National Electrical Code require a minimum size of 8 A...

Страница 8: ...e potential between the system neutral and ground will increase causing the meter to display the fault level which may be any value between 0 and 100 of 5A This current is also being monitored by the...

Страница 9: ...50 IGMAX 8 UP 9 UP 10 UP CURRENT 5A 1000 1 CT 1 DOWN 2 DOWN 3 DOWN 4 DOWN 5 DOWN 6 DOWN Figure 6 GFR RM Dipswitch 4 MAINTENANCE Gemini is designed and constructed to operate properly with minimal mai...

Страница 10: ...system DANGER Hazard of Electrical Shock Burn or Explosion Qualified personnel must perform testing referred to in this manual All power should be disconnected prior to making any connections or disco...

Страница 11: ...rs cables and rotating machines 2 To reduce mechanical stresses in circuits and apparatus carrying fault currents 3 To reduce electric shock hazards to personnel caused by stray ground fault currents...

Страница 12: ...current rating of the grounding impedance In no case shall the neutral conductor be smaller than No 8 copper or No 6 aluminum or copper clad aluminum c System Neutral Connection The system neutral con...

Страница 13: ...ing of the protective device on the system 4 Neutral grounding devices shall have insulation voltages at least equal to the line to neutral voltage 10 1106 Location of Neutral Grounding Devices and Wa...

Страница 14: ...hrough a resistor at the power source to limit the prospective ground fault current to 25 A or less b A grounding circuit shall originate at the grounded side of the resistor and extend along with the...

Страница 15: ...M SIGMA Resistor Monitoring and Ground Fault Relay C 322 MGFR Ground Fault Relay Manual C 409 DSP OHMNI High Resistance Grounding System Manual C 102 Gemini High Resistance Grounding System Manual C 1...

Страница 16: ...7615 Kimbel St Unit 1 Mississauga Ontario Canada L5S 1A8 Phone 905 673 1553 Toll Free 1 800 737 4787 Fax 905 673 8472 e mail sales i gard com www i gard com the power to protect...

Отзывы: