I-GARD Gemini Instruction Manual
4
24"
20"
1 3/4"
1 1/2"
1/4"
8 1/4"
Ø7/8"
PROVISION
FOR 1/2"
CONDUIT
A
IPC RESISTORS INC.
1-87-RESISTOR
PRESS TEST BUTTON TO SIMULATE GROUND FAULT AND OPERATE
CONTROL CIRCUITS.
GREEN LIGHT TURNS OFF,RED AND AMBER LIGHTS TURN ON.
PRESS RESET BUTTON AFTER TEST TO RETURN TO NORMAL.
GREEN LIGHT TURNS ON, RED AND AMBER LIGHTS TURN OFF.
1.
2.
3.
4.
TEST
WHEN GROUND FAULT ACTIVE LIGHT OR GROUND FAULT OCCURRED
IS ON;
ISOLATE AND DISCONNECT FAULTY CIRCUIT.
PRESS RESET BUTTON TO REMOVE FAULT CONDITION.
GREEN LIGHT INDICATES NORMAL CONDITION AND EQUIPMENT
ENERGIZED.
RED LIGHT INDICATES GROUND FAULT ON SYSTEM.
AMBER LIGHT INDICATES A GROUND FAULT HAS OCCURED AND
CLEARED.
NORMAL OPERATION
GROUND DETECTION
1.
2.
3.
1.
2.
RESET
TEST
G
SYSTEM
HEALTHY
A
TRIP
INDICATING
LIGHTS
FAULT
CURRENT
RESISTOR
FAULT
GROUND
FAULT
R
A
Figure 2 Wiring Diagram for Gemini
Figure 3 Outside Dimensions
CONTACT OPENS AT 110 ° C.
AND CLOSES AT 102 ° C.
301
HEAT SENSOR
NOTES:
1) ALL CONTACTS SHOWN IN THE
DE-ENERGIZED STATE.
2) ALL WIRING No. 14 AWG SIS GREY
UNLESS OTHERWISE STATED.
FOR CUSTOMER USE
AUXILIARY CONTACTS
8
9
8
9
GNDF
101
102
201
202
200
13
14
2
10
7
6
6
8
TRIP
1
TRIP
3
TRIP
90
97
FAN 2
FAN 1
G
LT4
1
2
60
40
LT1
R
1
2
SYSTEM
HEALTHY
SYSTEM
TRIP
12
300
7
11
21
20
L
1
11
10
9 10
2
1
NGRF
120 V.A.C. SUPPLIED BY
OTHERS.
TEST
11
4
NGRF
100
2
3
CB500
}
TO SYSTEM
GROUND.
No. 8 AWG MIN.
(GREEN)
GROUND
FAULT
13
9
8
11
N
RESISTOR
FAULT
}
5
6
10
TO SYSTEM
NEUTRAL.
No. 8 AWG MIN.
(WHITE)
30
G
NGRS6
2 x 3 x
FDL45000
11
12
13
12
RESET
N
R
G
19
20
21
22
17
16
GNDF
10
2
2
10
6
5
TRIP
50
GNDF
1
3
80
R
1
2
LT3
GROUND
FAULT
1
3
NGRF
R
1
2
70
LT2
RESISTOR
FAULT
NGRF
6
8
8
6
GNDF
95
96
23
24
7
8
0-100%