3. INSTALLATION
A typical installation will include for each power source (transformer/generator) 1 DSP-TDM, 1 DSP-DCM, 1 DSP-DPS,
1 DSP-DSM, 1 DSP-DRM and a number of DSP-DFM feeder modules as required with 1 for each branch protected.
Additionally there will be a DSP-OHMNI-PM pulsing resistor to ground the system. A voltage-sensing resistor DDR2 is
required for the DSP-DSM input, as well as one current sensor for each DSP-DFM for current detection. See Table 2
for typical requirements.
Catalogue Number
Description
Number Required/System
DSP-TDM
Display Module
1 (part of DSP-DSYS/v2)
DSP-DCM
Converter Module
1 (part of DSP-DSYS/v2)
DSP-DPS/v2
Power Supply
1 (part of DSP-DSYS/v2)
DSP-DSM/v2
System Voltage Module
1 (part of DSP-DSYS/v2)
OHMNI-PM
Pulse Equipped Resistor
1
DDR2
Voltage Sensing Resistor
1
Table 3: Optional Modules
Catalogue Number
Description
Number Required /System
DDAI
Artificial Neutral
Required only for delta system
DSP-DFM/v2
Feeder Module
As required 1/circuit(feeder)
TxA or Rx-yA
Toroidal Current Sensor
1/feeder module
DSP-ADM
Arc Detection Module
1 required for arc detection application
DSP-CA
Cable adapter module
1 required for Main-Tie-Main applications
DSP-CAS
Cable adapter module (switch)
1 required for Main-Tie-Main applications
Table 4: Standard Ribbon Cables
Length
Function
Catalogue Number
5cm (2 in.)
Module to Module connection
RC-3
30cm (12 in.)
Module to Module connection
RC-30
DSP modules are mounted on a 35mm DIN rail generally located at the rear wall of a switchgear compartment. They
should be mounted side by side and connected with 20-conductor ribbon cable in a daisy chain configuration. This ap
-
plies to the DSP-DPS, DSP-DSM and DSP-DFM modules only. DSP (outline dimensions). Care should be taken not to
over tighten the 8-32 nuts used to retain the DSP-TDM.
It will be necessary to provide a reliable power source (which is not interrupted by operation of the DSP output con-
tacts) for control power. The supply should be in the range of 120V to 240V AC, 50/60Hz or 125V DC up to 250V. The
control supply must be fused by a 1 ampere fuses as shown in Fig. 5 (Connection Diagram).
Table 2: System Module Requirements
Содержание DSP-OHMNI
Страница 1: ...C EG30EM Instruction Manual V2 June 2020 DSP OHMNI ...
Страница 11: ...9 Figure 1b DSP DCM Wiring Figure 1c System Module DSP DSM Wiring ...
Страница 12: ...10 Figure 1d Power Supply DSP DPS Wiring Figure 2 Preferred Feeder Module DSP DFM Wiring ...
Страница 45: ...43 Figure 41 DSP DPS System Module Connection ...
Страница 46: ...44 Figure 43 DSP DLM Logging Module Connections Figure 44 DSP TDM Display Module Connections ...
Страница 47: ...45 Figure 45 Typical DSP DRM Installation Connections ...
Страница 50: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...