If a feeder module is configured to a particular I/D number, it must also have a defined TRIP setting. The trip mode
must either be TRIP on 2nd fault or TRIP on first fault. The default is TRIP on 2nd fault. Click the trip mode drop down
to change the trip mode to TRIP on 1st fault. Each feeder module must be given a trip mode setting as either TRIP
on 1st fault or TRIP on 2nd fault. It is possible to have a DSP sytem where some feeder modules are programmed to
TRIP on 1st fault and some programmed to TRIP on 2nd fault.
The feeder module PRIORITY setting is set if it is TRIP on 2nd fault and DELAY setting is set if it is TRIP on 1st fault.
The priority numbers range from 00 to 15 with 0 being a lower priority than 15. In the case of priority numbers, it is OK
to use the same number more than once unlike the I/D numbers. For example, unimportant circuits can all be set to
00 and the critical feeder set to priority 15.
Note: It is possible to exceed the range of 00-15 and enter priority numbers above 15 but the priority will not be
increased and will roll over after 15 to become 00 again. To avoid confusion, the priorities should be kept within the
range 00 to 15 only.
The DELAY numbers range from 00 to 99 representing the delay for first-fault tripping in minutes or hours with 00
representing instantaneous TRIP operation (100 ms).
When all the fields for a given I/D number have been filled, press Program Feeder Module. You will then be prompted
with the screen of Figure 15.
Figure 15: Feeder Module Set-up
At this point, select the DSP-DFM module intended to have the I/D that was set-up, and press the TEST button on
that module. The red FAULT light will blink to indicate the received I/D signal (no need to hold button). Press ENTER
to complete the process. If the setup of the DSP-DFM is successful then the DSP-TDM will display the message in
Figure 16.
Should the DFM not be accepted, inspect the connections to the DSP-DFM as a ribbon cable connector may be loose
and could be preventing the DM from properly communicating with the DFM.
Содержание DSP-OHMNI
Страница 1: ...C EG30EM Instruction Manual V2 June 2020 DSP OHMNI ...
Страница 11: ...9 Figure 1b DSP DCM Wiring Figure 1c System Module DSP DSM Wiring ...
Страница 12: ...10 Figure 1d Power Supply DSP DPS Wiring Figure 2 Preferred Feeder Module DSP DFM Wiring ...
Страница 45: ...43 Figure 41 DSP DPS System Module Connection ...
Страница 46: ...44 Figure 43 DSP DLM Logging Module Connections Figure 44 DSP TDM Display Module Connections ...
Страница 47: ...45 Figure 45 Typical DSP DRM Installation Connections ...
Страница 50: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...