16
Figure 10 shows the first set-up screen that will be encountered – COMMS set-up mode. The DSP-OHMNI is normally
shipped with a 57600 Baud setup.
The DSP system must be identified by an address number from 01 to 32, to distinguish between it and other MOD
-
BUS devices that may be connected on the same MODBUS network. If only one device is used then it will typically be
set to 01, which is the default value (ensure that no other device has the same I/D setting on the MODBUS network or
data will not be valid). In order to change the number, select the field and enter the desired number. Then, press Save
Device ID.
NGR & Alarm Settings
To change the NGR & Alarm Setttings enter in the Admin mode, and from the HOME screen, press Settings
▸
NGR
and Alarm Settings.
6. ALARM SETTINGS
Figure 12: Grounding Resistor Set-up
Figure 11: Communications Set-up MODBUS RTU
Содержание DSP-OHMNI
Страница 1: ...C EG30EM Instruction Manual V2 June 2020 DSP OHMNI ...
Страница 11: ...9 Figure 1b DSP DCM Wiring Figure 1c System Module DSP DSM Wiring ...
Страница 12: ...10 Figure 1d Power Supply DSP DPS Wiring Figure 2 Preferred Feeder Module DSP DFM Wiring ...
Страница 45: ...43 Figure 41 DSP DPS System Module Connection ...
Страница 46: ...44 Figure 43 DSP DLM Logging Module Connections Figure 44 DSP TDM Display Module Connections ...
Страница 47: ...45 Figure 45 Typical DSP DRM Installation Connections ...
Страница 50: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...