HYUNDAI SINGLE PHASE VECTOR INVERTER

18

|

19

Notes on Use: Installation Location and Operating Environment

Notes on Use: Main Power Supply

Notes on Peripheral Equipment Selection

Avoid installation in areas of high temperature, excessive humidity, or where moisture can easily condense, as well as areas that are dusty, subject to corrosive 
gasses, mist from liquid used for grinding, or salt. Install the inverter in a well-ventilated and vibration-free room avoiding direct sunlight. 

The inverter can be operated in an ambient temperature range of -10

to 50

(carrier frequency and output current must be reduced between 40

to 50

).

An inverter run by a private power generator may overheat the generator or suffer from a deformed output voltage waveform from the generator.

Generally, generator capacity should be at least five times that of the inverter (kVA) in a PWM control system, or six times greater 
in a PAM control system.

Using a 
private power
generator

Installation of 
an AC reactor 
on the 
input side

(1) Be sure to connect main power cables to L1, L2 (input) terminals and motor to U, V, and W terminals (output). 

(Incorrect connection will cause a breakdown.)   

(2) Be sure to ground the inverter frame using the ground terminal.

If an electromagnetic contactor is installed between the inverter and the motor, do not perform on-off switching during running operation.

Install a circuit breaker on the main power input side to protect inverter wiring and ensure personal safety.

Choose an inverter-compatible circuit breaker.

If the earth leakage relay (or earth leakage breaker) is used, it should have a sensitivity level of 15 mA or more (per inverter).

Do not use a capacitor for power factor improvement between the inverter and the motor because the high-frequency 
components of the inverter output may overheat or damage the capacitor.

Wiring connections

Wiring 
between 
inverter 
and 
motor

Installing a circuit breaker

Earth leakage relay

Phase advance capacitor

Electromagnetic contactor

Thermal relay

Wiring distance

High-frequency components are included in the input/output of the inverter main circuit, and they may cause interference in a transmitter,
radio, or sensor if used near the inverter. The interference can be minimized by adopting noise filters (option).

The switching action of an inverter causes an increase in leakage current. Be sure to ground the inverter and the motor.

Because a smoothing capacitor deteriorates as it undergoes internal chemical reaction, it should
normally be replaced every five years. Be aware, however, that its life expectancy becomes considerably
shorter when the inverter  is subjected to such adverse factors such as high temperature, or heavy load
exceeding the rated current of the inverter.

Also, consumable parts such as cooling fans should be replaced according to the inverter periodic
inspection of the maintenance guide (maintenance inspection and parts replacement must be performed
by only specified trained personnel).

High-Frequency Noise and Leakage Current

Lifetime of Primary Parts

In the cases below involving a general-purpose inverter, a large peak current flows on the main power supply side, and is able to destroy 
the converter module. Where such situations are foreseen or the connected equipment must be highly reliable, install an AC reactor between 
the power supply and the inverter. Also, where influence of on indirect lightning strike is possible, install a lightning conductor.

(a) The unbalance factor of the power supply is 3% or higher(Note).
(b) The power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500kVA or more).
(c) Abrupt power supply changes are expected.

examples

: (1) Several inverters are interconnected with a short bus.   (2) A thyristor converter and an inverter are interconnected with a short bus.

(3) An installed phase advance capacitor opens and closes.   

In cases (a), (b) and (c), it is recommended to install an AC reactor on the main power supply side.

When used with standard applicable output motors (Hyundai standard three-phase squirrel-cage four-pole motors), the N50 Series 
do not need a thermal relay for motor protection due to the internal electronic protective circuit. A thermal relay, however, should be used:
(a) during continuous running at a range beyond 30 to 60 Hz.
(b) for motors exceeding the range of electronic thermal adjustment relay for each motor.
(c) when several motors are driven by one inverter; a thermal relay should be installed for each motor.

The RC value of the thermal relay should be more than 1.1 times the rated current of the motor. Where the wiring length is 10m or
more, the thermal relay tends to turn off readily. In this case, provide an AC reactor on the output side or use a current sensor.

The wiring length between the inverter and the remote operator panel should be 20 meters or less.

When this length is exceeded, use CVD-E (current-voltage converter) or RCD-E (remote control device).

Shielded cable should be used for the wiring. Be careful about the cable length to avoid line-voltage drop
(A large voltage drop causes a decrease in torque).

Содержание HiRun N50 Series

Страница 1: ......

Страница 2: ... only at high speeds but also low speeds in its driving characteristics Convenient for users through development of various optional products N50 Series name Applicable maximum motor rating 0 75 1 5 2 2 kW Input power rating single phase 200 V class 007 SF Model Number Information Motor kW Singlephase 200Vclass 0 75 1 5 2 2 Series Type ...

Страница 3: ...E We build a better future C O N T E N T S Features 04 External Dimension Diagram 05 Operation 06 General Specifications 07 Function List 09 Protective Functions 14 Terminal Functions 15 Application Wiring Apparatus Option 16 Option 17 Proper Operation 18 ...

Страница 4: ... by rapid speed restoration characteristics Applicable to the transfer machine treadmill industrial washing machine due to its function of momentary current suppression Possible to select various operation methods It is possible to select the operation methods of either RS485 communication driving or analog signal driving for the user s convenience Compact size for simplicity to install Reduction ...

Страница 5: ...n Table External Dimension Diagram Type Weight kg External Dimension mm W H D Installation Dimension mm W H 80 142 135 70 130 M4 1 0 1 3 85 130 M4 95 142 135 007SF 015SF 022SF 80 142 135 V I RS 485 CM1 CM2 5 4 3 2 1 FM H L T1 O OI RUN FUNC STR STOP RESET MIN MAX L1 L2 P RB U V W 1 220V POWER A RUN PRG Hz 007SF 135 95 142 V I RS 485 CM1 CM2 5 4 3 2 1 FM H L T1 O OI RUN FUNC STR STOP RESET MIN MAX L...

Страница 6: ...e A group appears A 01 appears Turn on the power Press the FUNC key Display A mode using the UP DOWN key Set the frequency using the UP DOWN key Press the FUNC key Press the STR key Press the FUNC key Press the UP key three times 0 0 or previously monitored value is displayed The motor rotates at the frequency set by the volume The motor stops Turn on the power Press the RUN key and adjust the vol...

Страница 7: ...urve Operating current level setting possible 20 200 enable disable selection Operating current level constant enable disable selection DC 0 5 V or DC 0 10 V 4 20 mA 10 40 no freezing 90 RH or less non condensing 20 60 short term temperature during transport Indoors without corrosive gases flammable gases oil mist or dust Maximum 1000m or less above sea level 5 9 m s2 or less Forced cooling IP20 V...

Страница 8: ...age Input selection of frequency setting current signal Self protection selection of start signal Contact input for when stopping the inverter with external terminal Thermal contact input for when stopping inverter with externally mounted thermal relay Control panel or external operation transition selection programmable V f control or sensorless vector control method selection programmable Multis...

Страница 9: ...ip event Previous 1 trip event Previous 2 trip events Previous 3 trip events Trip accumulation count 0 00 99 99 Hz by 0 01 Hz 100 0 400 0 Hz by 0 1 Hz 0 1 999 9 sec by 0 1 sec 1000 3000 sec by 1 sec 0 1 999 9 sec by 0 1 sec 1000 3000 sec by 1 sec 0 forward 1 reverse Setting range A01 A65 Setting range b01 b17 Setting range C01 C23 Setting range H01 H15 10 0 10 0 Output frequency monitor Output cur...

Страница 10: ... 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 5 10 00 Hz by 0 01 Hz 0 free run 1 deceleration stop 2 DC braking Frequency commanding RUN commanding Base frequency setting Maximum frequenc...

Страница 11: ... 1 100 0 by 0 1 sec 0 0 100 sec by 0 1 sec 0 0 100 sec by 0 1 sec 0 1 1000 0 by 0 1 sec 0 current input 1 voltage input 0 constant on 1 constant off 2 off during deceleration 0 1 999 9 sec by 0 1 sec 1000 3000 sec by 1 sec 0 terminal 2CH 1 transition frequency A57 A58 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 linear 1 S curve 2 U curve 0 linear 1 S curve 2 U curve Voltage offset Voltage ...

Страница 12: ... 0 Korea version 1 Europe version 2 US version 0 SUB reduced torque characteristic 1 CRT constant torque characteristic 0 overload overvoltage restriction mode OFF 1 overload restriction mode ON 2 overvoltage restriction mode ON 3 overload overvoltage restriction mode ON Deceleration rate when inverter restricts overload 0 1 10 0 sec by 0 1 sec 0 All parameters are locked when SFT from terminal is...

Страница 13: ...requency setting PID deviation level setting 1 2 3 8 0 0 0 0 0 1 0 0 100 0 0 0 100 0 0 00 10 0 0 0 0 0 3 0 0 00 0 00 0 0 1 2 250 0 10 0 200 0 400 0 400 0 100 0 Hz Hz 0 NO 1 NC 0 output frequency 1 output current 2 output voltage 0 45 250 220 by 1 3 0 10 0 by 0 1 0 5 inverter rated current 2 0 inverter rated current 0 0 400 Hz by 0 01 Hz 0 100 by 0 01 0 5 0 NO 1 NC 0 NO 1 NC 0 NO 1 NC 0 NO 1 NC 0 N...

Страница 14: ...OM error External trip Temperature trip Function Display Standardoperator Remoteoperator Description When the inverter output current exceeds the rated current by more than approximately 200 while the motor is locked or reduced in speed the protection circuit activates halting inverter output When the inverter output current causes the motor to overload the electronic thermal trip in the inverter ...

Страница 15: ... Output frequency meter output current meter output voltage meter Power supply for frequency setting Voltage frequency command signal Current frequency command signal Common terminal for frequency command Intelligent output terminal Run status signal RUN frequency arrival signal FA1 Set frequency arrival signal FA2 overload advance notice signal OL PID error deviation signal OD and alarm signal AL...

Страница 16: ... power capacity exceeds 500 kVA or when a sudden power voltage variation occurs It also helps to improve the power factor Vibration may increase when driving a general purpose motor with an inverter as compared with commercial power operation Connecting this reactor between the inverter and the motor allows reduction of motor pulsation When the cable between the inverter and the motor is 10 m or m...

Страница 17: ...UN FUNC STR STOP RESET POWER RUN PRG A Hz STOP RESET key This key is use for stopping the motor or resetting errors RUN LED On when the inverter is running Power LED On when the inverter power is inputted Display part LED display Displays frequency motor current motor rotation speed alarm history and setting value RUN key Press this key to run the motor This key works only when LED is on FUNCTION ...

Страница 18: ...motor base Under continuous low speed operation oil lubrication can deteriorate in a power transmission mechanism with an oil type gear box gear motor or reducer Consult the motor manufacturer for the permissible range of continuous speed To operate at more than 60 Hz confirm the machine s ability to withstand the centrifugal force generated Application to General Purpose Motors Run or stop of the...

Страница 19: ...ernal chemical reaction it should normally be replaced every five years Be aware however that its life expectancy becomes considerably shorter when the inverter is subjected to such adverse factors such as high temperature or heavy load exceeding the rated current of the inverter Also consumable parts such as cooling fans should be replaced according to the inverter periodic inspection of the main...

Страница 20: ... Grove London W6 0LG UK Tel 44 20 8741 0501 Fax 44 20 8741 5620 Tokyo 8th Fl Yurakucho Denki Bldg 1 7 1 Yuraku cho Chiyoda gu Tokyo 100 0006 Japan Tel 81 3 3212 2076 3215 7159 Fax 81 3 3211 2093 Osaka I Room 5th Fl Nagahori Plaza Bldg 2 4 8 Minami Senba Chuo Ku Osaka Japan 542 0081 Tel 81 6 6261 5766 5767 Fax 81 6 6261 5818 Dubai Level 2 Unit 205 Emaar Square Bldg 4 Sheikh Zayed Road P O Box 25245...

Отзывы: