HYUNDAI INVERTER N100
plus
Application Wiring Apparatus & Options
1. Field wiring connection must be made in accordance with a UL-listed and CSA-certified
closed-loop terminal connector sized for the wire gauge required.
Connector must be fixed using the crimping tool specified by the connector manufacturer.
2. Properly select the capacity of the circuit breaker to be used.
3. Check power wire size if cable length exceeds 20 m.
4. Use 0.75 mm
2
wire for the alarm signal wire.
Fuse
Thermal
Relay
Electro-
magnetic
contactor
(MC)
Name
Function
Input-side AC reactor for
harmonic suppression/
power coordination/
power improvement
This is useful when harmonic suppression measures must be taken,
when the main power voltage unbalance rate exceeds 3% and the
main power capacity exceeds 500 kVA, or when a sudden power voltage
variation occurs. It also helps to improve the power factor.
Reduces the conductive noise on the main power wires generated
from the main power supply.
Connect to the inverter primary side (input side).
This is installed between the inverter and the motor to reduce noise
radiated from the main control power wiring. It is useful for reducing
radio-wave disturbance in a radio or TV sets and preventing malfunction
of measuring instruments or sensors.
Vibration may increase when driving a general-purpose motor with
an inverter as compared with commercial power operation.
Connecting this reactor between the inverter and the motor allows
reduction of motor pulsation. When the cable between the inverter
and the motor is 10 m or more, inserting the reactor prevents thermal
relay malfunction caused by harmonics resulting from inverter switching.
A current sensor can be used instead of the thermal relay.
EMI filter
Output noise filter
AC reactor for vibration
reduction/thermal relay
malfunction prevention
Standard Apparatus (3-Phase input reference)
Options
Motor
output (kW)
0.4
0.75
1.5
2.2
3.7
0.4
0.75
1.5
2.2
3.7
N100
plus
-004SF
N100
plus
-004LF
N100
plus
-007SF
N100
plus
-007LF
N100
plus
-015SF
N100
plus
-015LF
N100
plus
-022LF
N100
plus
-037LF
N100
plus
-004HF
N100
plus
-007HF
N100
plus
-015HF
N100
plus
-022HF
N100
plus
-037HF
1.25 mm
2
2.0 mm
2
3.5 mm
2
0.14 mm
2
~
0.75 mm
2
shielded cable
5A
30A
20A
15A
10A
5A
15A
10A
0.14 mm
2
~
0.75 mm
2
shielded cable
2.0 mm
2
1.25 mm
2
Inverter model
(N100
plus
Series)
Wiring
Applicable equipment
Fuse (class J)
Power lines
Signal lines