Configuration
18. Click on the newly created alarm labelled “Disabled”.
19. Click the enabled check box and give the alarm a name, e.g. “Low level Alert”.
20. Now choose “Water Level” sensor as a source.
21. In the trigger box enter 3.5 and in the reset box enter 3.6.
22. Click the Call check box to get the iRIS to make a call-in when the event occurs.
23. The Alarms Configuration should look like this:
24. Repeat this for the high level alarm, but this time name it “High level Alert”, use a trigger of 17 and a reset of 16.9. The
Alarm Configuration should look like this: