Configuration
End Time:
Enter the time after which the iRIS must stop establishing wireless IP sessions.
Duration:
This is the length of time in seconds that you want the iRIS to keep each wireless IP session
active.
On Interval:
Enter the length of time in minutes between each successive wireless IP session being
established or an SMS message being sent when the time is in the “on” period (i.e. between the
start and end times).
Off Interval:
Enter the length of time in minutes between each successive wireless IP session being
established or an SMS message being sent when the time is in the “off” period (i.e. before the
start time or after the end time). This setting will normally be 0 (no activity), but this option
allows a different connection rate to be configured if required.
Alarm Interval:
Enter the length of time in minutes between each successive wireless IP session being
established or an SMS message being sent – when there are one or more active alarms in the
iRIS.
3.4.4.4.3 Cellular Modem - FTP 1 & FTP 2
The iRIS allows the push of data to up to two FTP servers and this is done in the FTP1 an FTP2 configuration tabs, both are
identical in format and operation so only one is shown below. If one or both are not needed simply remove the check
from the enable box.