Page 58
Submenu „Blow-down“ (Group 2)
Submenu „Service“ (Group 3)
Submenu „Governing“ (Group 4)
Par.
Denomination
Setting options
Code
2-1
Correction partial blow-down
-5...+5
Fs = 0
10
2-2
Correction full blow-down
-5...+5
Fs = 0
10
2-3
Switch stand-by blow-down
0=off, 1=on
Fs =
1
10
2-4
Waiting time stand-by blow-down
[h]
0.1...48.0
Fs = 24.0
10
2-5
Switch dead leg flushing
0=off, 1=on
Fs = 0
10
2-6
Interval dead leg flushing [h]
0.1...96.0
Fs = 24.0
10
2-7
Duration deadleg flushing [s]
1...600
Fs = 90
10
2-9
Steam-down time
0...250
WV=240
10
Par.
Denomination
Setting options
Code
3-1
Reset service interval steam
amount
0=no, 1=yes
Fs = 0
10
3-2
Reset K1 service interval
0=no, 1=yes
Fs = 0
10
3-3
Service interval [t]
0...90.0
Fs = device dependant
10
3-4
Service interval [tn. sh.]
0 ...99.9
Fs = device dependant
10
Par.
Denomination
Setting options
Code
4-1
Set point r.h. [%] (PI controller
only)
5...99.9
Fs = 50.0
10
4-2
Gain [%] (PI controller only)
0.1...99.9
Fs = 5.0
10
4-3
Integral [%] (PI controller only)
0...100.0
Fs = 10
10