Page 33
Switch on t he un it and check for leaks af ter 15-30 minutes of
operation.
If leakage occu rs, switch of f power su pply and follow safety
instructions for work on live components.
8.4 Electrode wear
Electrode wear depends on:
•
feed water composition and conductivity.
•
the quantity of steam produced.
Warning:
At the latest, electrodes must be replaced if a mainte-
nance message is displayed. The
maintenance message
appears af ter one hour o f ope ration at maximu m wate r level.
The hu midifier switches it self of f. Also see Se ction "Ma inte-
nance." Whe n the ele ctrodes are less than 1/3 to 1/ 2 of their
original length, replace them.
8.4.1 Original Electrode Lengths
Original lengths of HygroMatik large area st ainless-steel e lec-
trodes are:
HyLine:
CompactLine:
MiniSteam:
Type
HY05-HY08 HY13-HY60 HY90-HY116
Length
[mm]
155
235
300
Type
C6 C10 C17-45 C58
Length [mm] 125 155
235
300
Type
MS5
MS10
Length [mm]
125
155