background image

P/N 42-9540 11/12 Copyright 2012 Hydrotherm

Page 13 

KN INSTALLATION INSTRUCTIONS FOR VENT AND AIR PIPING

Figure 8 

(repeated from page 10)

Combustion air must be uncontaminated

 

Construction dust

: If the boiler is operated while the building 

is under construction it must be protected from wood, concrete, 
sheet rock and other types of dust. Failure to properly protect 
the boiler from construction dust will damage the boiler. 

 

Combustion air contaminated with fl uorocarbons  or 
other halogenated compounds,

 such as laundry products, 

cleaning solvents and refrigerants will result in the formation of 
acids in the combustion chamber and vent piping. Th ese acids 
will cause premature failure of the boiler and vent, causing 
possible severe personal injury, death or substantial property 
damage.

 

If the boiler room, or any room through which the air piping 
travels, may contain 

contaminants

 as listed above, you 

MUST 

seal air pipe joints with silicone RTV

 to prevent contaminants 

from entering the boiler combustion air. Th e fi nished air piping 
installation must be air-tight and water-tight.

Air piping 

(see Figure 3)

8 — Air pipe connection

 

Construct the air piping from PVC, CPVC or ABS plastic, or galvanized or 
aluminum metallic pipe (including fl exible aluminum duct if desired).

  When using metallic piping — seal all of the longitudinal seam joints in 

addition to the component joints.

 

Att ach the air piping to the boiler air connection, requiring use of silicone RTV 
to seal the connection. If the boiler room air is free of contaminants you can use 
metallic duct tape to seal the joints. With age, however, duct tape adhesives can 
loosen, so duct tape is not as reliable as silicone RTV.

 

If the installation is required to meet direct vent (sealed combustion) requirements, 
seal all joints with silicone RTV. Th e air pipe installation must be air-tight and 
water-tight.

 

Th e air piping connects to the stainless steel pipe section att ached to the air intake 
rain cap termination (item 

10

, Figure 8). See instructions following.

 

Maximum air piping length

 — See the table in Figure 8 for the maximum 

allowable length. Each elbow causes the same pressure drop as 10 feet of vent pipe, 
so the allowable length reduces 10 feet for each elbow used in the piping. When 
45° elbows are used, two 45° elbows are equivalent to one 90° elbow.

9 — Supporting air piping

 

DO NOT use the boiler air connection to support the air piping

. Provide 

support straps from the ceiling or install wall brackets.

 

Provide at least one support on all air pipe installations.

 

Provide a support every 3 feet for air pipe lengths greater than 5 feet horizontally.

 

Provide a support on the horizontal piping within 6 inches of every upturned 
elbow to support the vertical run.

Vent and air piped through the roof 

(separate terminations)

3

Содержание KN-2

Страница 1: ...stantial property damage The boiler can only be operated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with cont...

Страница 2: ...pingcomponentforHeat fabventpipe orgearclampsforvent pipe Neverusescrewsintheventpiping ScrewsareonlyappliedtotheairpipingportionofHeat fabSC concentric vent used for concentric vent air sidewall term...

Страница 3: ...KN 2 Vent components Heat Fab KN 4 Vent components Heat Fab Vent piping components incl supports thimbles etc EZ Seal 3 inch Vent piping components incl supports thimbles etc EZ Seal 4 inch Rain cap...

Страница 4: ...s Heat Fab Air components Heat Fab Termination elbow Same as vent termination Termination elbow Same as vent termination Air piping components also supports thimbles etc 3 inch PVC CPVC ABS galvanized...

Страница 5: ...rials could result in vent system failure Exposed vent pipe poses a potential burn hazard to people and pets Insulate or shield the pipe where necessary to prevent risk Never drill through or install...

Страница 6: ...piping completely DO NOT use the boiler vent connection to support the vent piping Provide support straps from the ceiling and pedestal supports from the floor utilize noncombustible saddle This is re...

Страница 7: ...operly install the vent piping could result in flue gas leakage causing possible severe personal injury death or substantial property damage Code compliance Follow all applicable local codes when inst...

Страница 8: ...se installations 3 4 Support the vent piping completely DO NOT use the boiler vent connection to support the vent piping Provide support straps from the ceiling and pedestal supports from the floor ut...

Страница 9: ...ding flexible aluminum duct if desired Whenusingmetallicpiping sealallofthelongitudinalseamjointsin addition to the component joints Attach the air piping to the boiler air connection requiring use of...

Страница 10: ...ar clamp manufactured by the vent manufacturer see Table 2 Slide the clamp over the male end of the pipe after the pipe has been inserted from outside From the inside pull the pipe so it is firmly aga...

Страница 11: ...roperly install the vent piping could result in flue gas leakage causing possible severe personal injury death or substantial property damage Code compliance Follow all applicable local codes when ins...

Страница 12: ...3 4 Support the vent piping completely DO NOT use the boiler vent connection to support the vent piping Provide support straps from the ceiling and pedestal supports from the floor utilizing noncombus...

Страница 13: ...ping sealallofthelongitudinalseamjointsin addition to the component joints Attach the air piping to the boiler air connection requiring use of silicone RTV to seal the connection If the boiler room ai...

Страница 14: ...If a longer length is required use a length of EZ Seal long enough for the application Attach the air piping to the male end bottom end of the stainless steel pipe C Roof penetration components Use th...

Страница 15: ...ode compliance Follow all applicable local codes when installing the vent system Where codes differ from this manual followcoderequirements ContactHydrothermifyou have any questions regarding the inst...

Страница 16: ...late the vent piping where it passes through unheated areas to prevent condensate freeze up Do not insulate the within 18 inches of the termination when it passes through a combustible wall If the pip...

Страница 17: ...application Insert the pipe from OUTSIDE male end first The pipe will stop at the raised section of the female end C Gear clamp Use a hose clamp or a gear clamp manufactured by the vent manufacturer s...

Страница 18: ...IONS FOR VENT AND AIR PIPING Figure 12 Termination minimum clearances Vent piped through a side wall combustion air from the boiler room cont 4 Figure 13 Using external piping to raise the termination...

Страница 19: ...ual followcoderequirements ContactHydrothermifyou have any questions regarding the installation Terminate the vent and air piping following the guidelines in this manual Avoid vent termination locatio...

Страница 20: ...ler Install at least one support on every horizontal run For horizontal runs longer than 5 feet 1 5 m install a support every 3 feet 0 9 m Ventpipingcannotbesupportedfromabove suchasrelyingonroofjacks...

Страница 21: ...IDE male end first The pipe will stop at the raised section of the female end C Gear clamp Use a hose clamp or a gear clamp manufactured by the vent manufacturer see Table 5 Slide the clamp over the m...

Страница 22: ...16 Vent termination minimum clearances see Figure 18 for required spacing between vent and air terminations Figure 17 Using external piping to raise the termination Figure 18 Minimum spacing between v...

Страница 23: ...s likely to be affectedbywinds snowdrifts peopleandpets Protectbuilding materials and vegetation from degradation caused by the flue gases and condensation Vent piping see Figure 19 1 Boiler vent conn...

Страница 24: ...on every horizontal run For horizontal runs longer than 5 feet 1 5 m install a support every 3 feet 0 9 m Ventpipingcannotbesupportedfromabove suchasrelyingonroofjacksections You must install supports...

Страница 25: ...nd the pipe B Length of concentric vent pipe Use a 1 foot length of vent pipe as listed in Table 6 unless the wall penetration quires a longer length If a longer length is required use a length of Hea...

Страница 26: ...e wall concentric termination cont 6 Figure 21 Termination minimum clearances see Figure 22 for required spacing between terminations Figure 22 Minimum spacing between terminations terminations must a...

Страница 27: ...P N 42 9540 11 12 Copyright 2012 Hydrotherm Page 27 KN INSTALLATION INSTRUCTIONS FOR VENT AND AIR PIPING 7...

Страница 28: ...IN UNITED STATES 260 NORTH ELM ST WESTFIELD MA 01085 413 564 5515 FAX 413 568 9613 IN CANADA 7555 TRANMERE DRIVE MISSISSAUGA ONT L5S 1L4 905 672 2991 FAX 905 672 2883 www hydrothermkn com...

Отзывы: