Programming operating mode sine wave
In this operating mode a sinusoidal curve, devided in three stages, can be defined.
The values in the shown dialog result in this sine wave:
A
amplitude of
the oscillation and corresponds to the Volt value as a percentage of the maximum output
voltage.
O
Offset
between zero and the baseline of the oscillation and corresponds to the Volt value as a percentage
of the maximum output voltage.
F
Frequency of
the oscillation - is given as a multiple of 10 mHz
Range
Value range
A
10%...100%
O
10%...100%
A+O
max. 100
F
0.01Hz... 2Hz...
A minimum offset of 10% is specified in this operating mode. The amplitude of the sine is added to the offset.
The value of 100% is not exceeded, nor is the value falling below 0%.
Make sure that the sum of
amplitude
and
offset
is less than 100%. A negative amplitude cannot be displayed.
Highlight the setting values of the curve, press and
enter the desired value and confirm with
.
Save and exit the setting with F5 .