- 9 - 

 

NOTE:  

If the button 

 is pressed during the modification phase, the input is 

interrupted and the changed figures not registered.  

 
 

Time Zones 

 
The switch-on and 

–off times of the unit can be programmed  in the menu „Time zones“ after 

the operation mode „Timer control“ was retrieved. One such setting is possible per day.  
 
A group of several days or also individual days can be programmed by the operator. Switch-
on and switch-off times are controlled and initiated by the internal timer.  
 
Groups: 

 

Mo ... Su 

(several days) 
 
 
 

 

 

Mo ... Fr 

 
 
 
 

 

 

Sa ... Su 

 
 
 
Individual days: 

Mo, Tue, Wed, Thu, Fr, Sa, Su 

 
 

 

 

 

 

 

 

    and so on 

– for every day in the week. 

 
 

An initial selection of the desired menu is possible via the Cursor buttons 

 , the 

menu is then retrieved by pressing the button 

 once and the switching times can then be 

altered via the Cursor buttons. The figure that can actually be altered is marked with a line 

underneath. Once the correct setting is achieved, the button  

 must be pressed until the 

line underneath is no longer visible. If the total switch settings for the selected and retrieved 

group of days /individual day are to be cleared, press the button  

 once.  

 
The times for switch-on and switch-off can be selected right on the dot. Below is an example 
for setting switch time - group of days Mo-Su, switch-on 6.00 a.m., switch-off 10.00 p.m.  
 
 
 
 
NOTE: 

 If times different to the individual days than provided in the corresponding 
group of days are set, the display for the group of days show **:**-**:** and the 
actual switch time is set in the day monitoring.  

 

If the switch-off time is set earlier than the switch-on time or if the times were 
reset (00:00-00:00), the water conditioning unit is not activated that day(s).  

Select time zone:

 

Mo .. Su:      **:** - **:** 

Select time zone:

 

Mo .. Fr:      **:** - **:** 

Select time zone:

 

Sa .. Su:      **:** - **:** 

Select time zone:

 

Mo:           **:** - **:** 

Alter time zone:

 

Mo .. Su:      06:00 - 22:00 

Содержание HY-MAG DN100

Страница 1: ... 1 HY MAG INTEGRAL DN100 Serial number HYDROTEC Hydrotec House 4 5 Manor Courtyard Hughenden Avenue High Wycombe HP13 5RE Tel 01494 796040 Fax 01494 796049 ...

Страница 2: ...r part dependent on nominal width Max operating temperature 80 C Nom Pressure PN 16 CAUTION The HY MAG Integral control box is designed in protection class IP65 The feed line with power supply plug for mains supply does not meet the requirements Mains supply line and plugs must rather be positioned outside the possible spray water range or be protected by appropriate means NOTE The HY MAG Integral...

Страница 3: ...r part has been closed The connection cable between control box and water part is a spiral cable Max distance between both unit components shall not exceed 1 5 m HY MAG DN100 The control box for the HY MAG DN100 does include a mains connection cable a load cable and a cable to connect the thermal protection The connection box terminal strip provided on the water part is necessary to make the appro...

Страница 4: ...peration check of complete HY MAG system control box and water conditioning unit The below individual sequences are shown Test thermal protection Actor test Temp test OK Test current to water conditioning unit See list of individual current rates for units nom width Pre set water conditioning unit example HY MAG DN100 Check remanence clearance H Y D R O T E C Integral V 1 00 Short circuit test Tes...

Страница 5: ...Operation state Monitoring current rate The current ratings for the corresponding HY MAG types are shown in the below list REFIT Phase Duration about 4 s magnetic remanence clearing LED extinguishes successively to the left within 4 seconds GREEN LED LED GREEN LED REFIT Phase YELLOW All 8 LED s light successively RED negative d c approx 100 V is released to the water part Duration about 26 s LED G...

Страница 6: ...nu levels Clear parameters Selection of individual menu sequences in menu levels modification and setting of parameters Selection of individual menu sequences in menu levels modification and setting of parameters Retrieval of individual menu sequences confirmation acknowledgement of settings NOTE The monitoring returns to Standard Mode if input is delayed for more than 30 seconds and standard oper...

Страница 7: ...he control box is in standby mode LED standby YELLOW Switch on and off times are controlled by the internal timers One switch on and off time per day can be programmed The above operation modes can be selected by subsequent pressing the buttons and the correct mode can then be confirmed and acknowledged by pressing the button once The control box and or monitoring returns automatically to main men...

Страница 8: ... previous display Clearing the relative operating hours results in an automatic store and monitoring of the actual time of clearing in line 2 Date Time The operator can alter the internal timer and the date as described below The main menu Date Time must initially be retrieved whereby the display shows the actual setting If the setting is to be altered press the button Should no modification be re...

Страница 9: ...r buttons The figure that can actually be altered is marked with a line underneath Once the correct setting is achieved the button must be pressed until the line underneath is no longer visible If the total switch settings for the selected and retrieved group of days individual day are to be cleared press the button once The times for switch on and switch off can be selected right on the dot Below...

Страница 10: ...ttons shall be pressed for 30 seconds after such time period the HY MAG Integral control box returns automatically to standard mode Failure Indication The Integral control box is provided with an automatic failure recognition whereby the failure type is shown In case of failure the total LED scale flashes red and the display shows the type of failure Moreover it is possible to signal a failure via...

Страница 11: ...itch in the coil of the HY MAG DN100 was released ATTENTION If the button is pressed during a failure record the acoustic alarm is switched off the record contact shows failure and the display Conditioning off A new start of the control box and initiation is released automatically about 60 seconds after a button has been pressed last Failure Undercurrent Thu 11 10 2003 16 17 Failure Overload Thu 1...

Страница 12: ... Failure 1 Undercurrent Check connection and correct fit between water part and control box i e fit of Harting coupling Failure 2 Overload Failure in magnet solenoid coil in water unit Inform Hydrotec immediately in that case since no further local steps are possible It is necessary to note the time the failure had been recognised first Disconnect unit from mains voltage Failure 3 Short cut Short ...

Страница 13: ...Failure 6 Overheating For HY MAG DN100 only Temperature safety control was released i e the solenoid coil in the water part is overheated Check whether or not exterior influences or stagnation of water may be the reason If there is no exterior influence visible control operation and check whether cooling takes place The operation mode starts automatically again once the coil temperature is cooling...