one  pump  starts.  Allow  pump 

to  operate  until  level  drops  

to turn-off point.

5.  Allow  sump  level  to  rise  to 

start  oth er  pump.  Notice  run 

lights on panel; pumps should 

alternate  on  each  suc ces sive 

cycle of op er a tion. 

6.  Turn  both  H-O-A  switch es  

to  Off  po si tion  and  allow  

sump  to  fill  to  the  over ride  

control level.

7.  Turn  both  switches  to  Auto  

po si tion and both pumps should 

start and op er ate to geth er until 

level drops to turn-off point.

8.  Repeat  this  operation  cycle 

sev er al times before leav ing job.

9.  Check  voltage  when  pumps 

are  op er at ing  and  check  the 

amp draw of each pump. On 3 

phase  pumps,  check  amps  on 

each wire as sometimes a high 

leg  will  exist.  One  leg  can  be 

some what  high er  (5  to  10%) 

without  caus ing  trou ble.  For 

excessive  voltage,  the  power 

com pa ny should be consulted.

As  the  motors  are  oil  filled,  no  

lu bri ca tion  or  other  main te nance 

is  required.  The  pump  should  be 

lifted  once  every  two  years  and 

the  oil  drained  from  the  motor 

chamber to check for water. 
generally  these  pumps  give  very 

re li able service and can be expected 

to  op er ate  for  years  on  normal 

sewage pump ing without failure.

Lightning:

In some areas where con sid er able 

light ning occurs, it is recommended 

that  a  light ning  arrestor  be 

installed at the con trol panel.
Complete  data  on  lightning 

arrestors  and  cost  are  avail able 

from  the  factory.  Light ning  ar res-

tors  are  good  in sur ance  against  

damage to an ex pen sive motor.

Servicing instructions:

iMPOrTAnT: 

read 

all  

in struc tions  be fore  replacing 

any parts.

WArning:  Before  han dling 

these pumps and controls, always 

dis con nect the power first.
Do not smoke or use sparkable 

elec   trical  devices  or  flames  in 

a  sep tic  (gas eous)  or  possible  

septic sump.

Field Service on Motor:

All  submersible  motors  can  be       

ser viced  (out  of  warranty)  in  the 

field by any reliable motor service 

shop.  Any  pump  (in  warranty) 

must  be  re turned  to  the  factory  

for  ser vice  or  repaired  in  an  

au tho rized  Hydromatic  ser-

vice  center.  Charges  will  not  be  

al lowed  if  (in  war ran ty)  pump  

is  taken  to  a  mo tor  repair  

shop  that  is  not  an  authorized  

Hydromatic service cen ter.
When  field  service  is  per formed 

on  a  pump,  these  in struc tions 

should be care ful ly followed.

replacing Stator:

If  motor  winding  is  burned  or 

shorted,  it  can  be  rewound  or 

replaced with new fac to ry wound 

stator. Refer to sec tion al draw ing 

of  pump  and  mo tor  and  use  the  

fol low ing  steps  to  re move  and 

replace sta tor.
1.  If  stator  only  is  damaged, 

it  may  not  be  necessary  to  

completely dis mantle pump as 

stator and hous ing can be lift ed 

from pump without dis turb ing 

seals or bear ings.

2.  Drain all oil from upper housing. 

If  oil  is  clean  and  no  water  is 

present,  seals  can  be  considered 

satisfactory to reuse.

3.  After  chamber  is  drained, 

remove  hold-down  bolts    and 

lift  off  motor  housing.  Use 

care in lifting.

4.  Set  assembly  on  bench  and  

re move  cord  cap  assembly  by 

removing  bolts.  When  this  is 

lift ed  off,  con nec tion  wires  to 

motor  will  be  exposed.  These 

wires will prob a bly be burned, 

but  each  wire  is  tagged  with  

a  metal  marker  giv ing  wire 

num ber. Cut the wires.

5.  If  the  leads  to  the  cord  cap  

as sem bly  are  burned,  the  

cord  cap  assembly  must  be  

re placed.

6.  After  stator  retaining  ring  is  

re moved, turn hous ing upright 

and bump on hard wood blocks. 

This should jar the stator loose 

and al low it to drop out.

Pump

Maintenance

Содержание S3SD

Страница 1: ...ase make sure you provide this manual to the owner of the pumping equip ment or to the responsible party who maintains the system Submersible Sewage Pump Dual Seal Pumps S3SD S4SD SB3SD SB4SD Part 5625 420 1 Item E 03 420 04 09 ...

Страница 2: ... panel Sump Level Control Sump level is controlled by Hydromatic 3900 mercury switch level controls The 3900 level controls is a metal case mercury switch sealed in a solid polyurethane float The float is held in position by a weight at tached to the power cord above the float The cord supports the float and is adjusted for height from the sur face Typical duplex systems use three floats the lowes...

Страница 3: ...ump Nema 4 Junction Box Optional If electrical control panel is to be set re mote from the pump sump a NEMA 4 junc tion box should be used to make pow er and control con nec tions The Hydromatic NEMA 4 junc tion box is pro vid ed with com pres sion con nec tors for seal ing all wires No sealing com pound is need ed to make con nec tions waterproof NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANE...

Страница 4: ... ces sive solids may collect for the pump to han dle A frequent pump ing cycle is rec om mend ed for best op er a tion If an alarm system is used this con trol is usually set about 6 inch es above the over ride control Some engineers as de scribed pre vi ous ly prefer to have the alarm control set be low the override control Making Electrical Connections All electrical wiring must be in ac cor dan...

Страница 5: ...ls always dis con nect the power first Do not smoke or use sparkable elec trical devices or flames in a sep tic gas eous or possible septic sump Field Service on Motor All submersible motors can be ser viced out of warranty in the field by any reliable motor service shop Any pump in warranty must be re turned to the factory for ser vice or repaired in an au tho rized Hydromatic ser vice center Cha...

Страница 6: ...l oil cov ers top of wind ings Leave air space in top for ex pan sion Use Permatex on plug threads Replacing Seals and Bearings 1 Drain all oil from motor chamber as described 2 Remove bolts that hold motor hous ing to bearing housing Re move screws hold ing bearing housing to volute housing 3 Lift rotating assembly rotor shaft and impeller from pump case and place hor i zon tal ly on bench With h...

Страница 7: ... on power and if pump starts trouble is in float con trol Replace control Pump Troubleshooting Pump runs but will not shut off 1 Pump may be air locked Turn pump off and let set for several min utes then restart 2 Lower float control may be hung up in the closed po si tion Check in sump to be sure control is free 3 Selector switch may be in the Hand position Pump does not deliver prop er capacity ...

Страница 8: ...te 1 18 00975 012 1 Snap Ring 1 19 08908 002 1 Key Square 1 20 10108 000 1 Washer Impeller 1 21 19101A003 Screw Cap 1 22 09927 123 2 Impeller 1 5 HP 1 09927 124 2 Impeller 1 HP 2 HP 1 09927 125 2 Impeller 3 HP 1 23 06106A019 Screw Cap 5 24 07990 002 2 Plate Seal 1 8 Ref Part Part No No Description Qty 25 00150 019 1 O Ring 1 26 19103A043 Screw Cap 4 27 08206 000 1 Inst Plate 1 28 07145 000 2 Housi...

Страница 9: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 23 22 24 25 30 29 28 27 38 26 23 31 15 32 33 34 35 36 37 9 S3SD ...

Страница 10: ...p Ring 1 19 08908 002 1 Key Square 1 20 10108 000 1 Washer Impeller 1 21 19101A003 Screw Cap 1 22 09927 123 2 Impeller 1 5 HP 1 09927 124 2 Impeller 1 HP 2 HP 1 09927 125 2 Impeller 3 HP 1 23 06106A019 Screw Cap 5 24 07990 002 2 Plate Seal 1 Ref Part Part No No Description Qty 25 00150 019 1 O Ring 1 26 19103A043 Screw Cap 4 27 08206 000 1 Inst Plate 1 28 07145 000 2 Housing Bearing 1 29 00568 007...

Страница 11: ...11 SB3SD 2 1 10 3 4 5 6 7 8 9 11 12 13 14 15 16 17 44 42 43 24 23 22 21 20 19 18 38 27 28 29 30 39 41 26 25 31 15 32 33 40 34 35 36 37 ...

Страница 12: ...16 00150 029 1 O Ring 1 17 09995 101 2 Volute 1 18 00975 012 1 Snap Ring 1 19 08908 002 1 Key Square 1 20 10108 000 1 Washer Impeller 1 21 19101A003 Screw Cap 1 22 09978 031 2 Impeller 3 HP 1 09978 031 2 Impeller 2 HP 5 HP 1 09978 129 2 Impeller 7 5 HP 1 23 06106A019 Screw Cap 5 Ref Part Part No No Description Qty 24 07990 003 2 Plate Seal 1 25 00150 023 1 O Ring 1 26 19103A043 Screw Cap 4 27 0820...

Страница 13: ...13 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 38 27 28 29 30 23 31 15 32 33 34 35 36 37 S4SD ...

Страница 14: ...7 09995 101 2 Volute 1 18 00975 012 1 Snap Ring 1 19 08908 002 1 Key Square 1 20 10108 000 1 Washer Impeller 1 21 19101A003 Screw Cap 1 22 09978 031 2 Impeller 3 HP 1 09978 031 2 Impeller 2 HP 5 HP 1 09978 129 2 Impeller 7 5 HP 1 23 06106A019 Screw Cap 5 24 07990 003 2 Plate Seal 1 25 00150 023 1 O Ring 1 Ref Part Part No No Description Qty 26 19103A043 Screw Cap 4 27 08206 000 1 Inst Plate 1 28 0...

Страница 15: ...15 2 1 10 3 4 5 6 7 8 9 11 12 13 14 15 16 17 44 42 43 24 23 22 21 20 19 18 38 27 28 29 30 39 41 26 25 31 15 32 33 40 34 35 36 37 SB4SD ...

Страница 16: ..._____________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ __________...

Страница 17: ..._____________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ __________...

Страница 18: ...operly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installatio...

Страница 19: ......

Страница 20: ...___________________________ D Incoming line voltage _________________________ Actual _____________________________ E Voltage to pumps ____________________________ Actual _____________________________ F Type of junction box _____________________________ Manufacturer _______________________ G Are floats installed in wet well _______________________________________________________ H Are floats set to...

Отзывы: