background image

4

Installation 

Instructions

NOTE:  If  using  flanged  

connections,  be  certain  that  

adequate 

clearances 

are  

provided  throughout  for  the 

installation  of  bolts,  nuts,  lock 

washers, and gaskets.

If  total  run  of  vertical  piping 

exceeds  twelve  (12)  feet,  install 

a piping brace at the approximate 

midpoint  of  the  piping.  Secure 

brace (i.e., U-bolt with angle iron 

strap and angle iron extensions) to 
both piping and wall of basin.

4. Basin Cover(s)

The  basin  cover  for  the  sump 

and  valve  box  can  either  be 

poured  concrete  or  precast. 

If  Hydromatic  door  and  frame 

assemblies  are  used,  locate  the 

concrete  openings  with  respect 

to  the  discharge  elbow  mounting 

studs  as  shown  in  the  Installation 

Data.  If  the  covers  are  poured, 

place the door and frame assembly 

inside  the  concrete  form  and 

position  per  installation  data. 

Anchor  straps  are  provided  on 

the door frames to secure them to 

the concrete. If precast covers are 

used,  remove  anchor  straps  from 

frame before installing into covers. 

Either  cast  four 

3

8

”  anchor  bolts 

into the top of the precast cover or 

drill holes for expansion lag screws. 

Use  either 

3

8

”  nuts  or  stainless 

steel bolts to secure door and frame 

assembly  to  cover.  If  valves  are 

to  be  inside  the  wet  well,  provide 

access  ways  as  required  for  the 

piping and valves to access piping 

shut-off  valves  (see  Installation 

Data  for  general  dimensions  of 

access ways). Access ways must be 

covered and secured with tamper-

proof hardware (by others).

5. Guide Rail Installation

Install  the  pultruded  guide  rail  

(I-beam)  by  attaching  the  lower 

end  of  the  guide  rail  to  the 

slotted lugs on the top side of the  

discharge  elbow.  Two 

3

8

”  x  2” 

bolts, one rectangular washer, lock 

washers,  and  nuts  are  provided 

with  the  discharge  elbow  parts 

package.  At  the  top  of  the  guide 

rail,  plumb  and  then  fasten  the 

guide  rail  to  the  door  &  frame 

assembly  or  other  suitable 

bracket,  using  the  four 

1

4

” 

x  1  stainless  steel  cap  screws. 

If  Hydromatic  door  and  frame 

assemblies  are  not  used,  obtain 

suitable  upper  guide  rail  brackets 

(by  others)  to  locate  and  support 

the rail(s). A flat surface 4” wide 

is required for each rail.

6. Intermediate Guide  

Rail Bracing

Sump  depths  of  9’6”  and  greater 

require  intermediate  guide  rail 

bracing.  The  braces  mount  on  

the  vertical  discharge  pipes  with 

U-bolts which are sized according 

to  the  discharge  pipe  size.  The 

number  of  guide  rail  braces 

required are as follows:

Sump Depths
9’6” to 18’0”  1 guide rail brace  

   

  required

18’6” to 27’0”  2 guide rail    

   

  braces required

27’6” to 30’0”  3 guide rail 

   

  braces required

On  depths  requiring  more  than 

one  brace,  space  the  braces  

equally  on  the  pipe  and  tighten  

U-bolts. Match drill two 

5

16

” holes 

through  the  guide  rail  flange  and 

attach with two 

1

4

” x 1” stainless 

steel bolts, nuts, and lock washers 

provided with braces. Install with 

bolt heads against the bracket.

7. Exterior Piping

Install  the  inlet  hub(s)  in  side 

of  basin  and  install  inlet  piping 

in  hub  and  grout,  or  install  inlet 

pipe(s)  directly  into  basin  and 

grout.  Install  drain  pipe  from 

valve  box  (if  required)  to  basin. 

Slope pipe to give proper drainage 

to basin. Install vent piping in side 

of  basin  (if  required).  Extend 

piping to a proper elevation above 

grade  (as  required  by  plans  and 

specifications and/or local codes). 

All  piping  furnished  by  others. 

See  Installation  Data  for  typical 

piping arrangement.

8.  Pump and Sealing Flanges

Assemble the sealing flange (with 

arms)  to  the  pump  discharge 

flange using a gasket between the 

two. Screw nuts with lock washers 

on  the  bottom  six  studs.  Slide 

the  guide  rail  connector  through 

the sealing flange ears and below 

the  top  two  studs  protruding 

through the back side of the pump 

flange. Place the retainer clips on 

the studs followed by lock washers 

and nuts and follow illustration.

9.  Pump Installation

Check  all  piping  braces  and  

supports  for  proper  installation 

and  tightness.  Attach  the  lifting 

chain  assembly  or  cable  to  the  

lifting  eye(s)  on  the  top  of  

the  pump  with  the  shackle(s)  

provided.  Lower  the  pump  into 

the  basin  with  the  guide  rail  

connector  engaged  over  the  

pultruded  guide  rail  (I-beam). 

Ensure  that  the  chain  or  cable 

does  not  interfere  with  the  cord 

cap  assembly.  Attach  the  upper 

end  of  lifting  assembly  to  the 

hook provided on the inside of the 

Hydromatic  door  and  frame.  The 

heavy  rubber  sealing  diaphragm 

on the pump discharge should not 

touch the discharge elbow flange 

when the pump is being installed 

or removed, or is installed but not 

Содержание PULTRUDED RAIL SYSTEM

Страница 1: ...To the installer Please make sure you provide this manual to the owner of the pumping equip ment or to the responsible party who maintains the system Part 5625 359 1 Item E 03 359 04 09 PULTRUDED RAIL SYSTEM ...

Страница 2: ...nge should release easily Step 2 Attach supplied chain leg to achieve a three point lift Test the balance of the pump by adjusting the location of the shackle in reference to individual chain links The pump must be level to function properly WARNING If the sealing flange end of pump is raised above the horizontal the guide rail may be damaged upon lowering the pump Ensure pump is horizontal before...

Страница 3: ...vertical discharge piping modules to elbow using bolts nuts lock washers and gasket NOTE When increasing the pipe size at the discharge elbow an eccentric flanged reducer coupling may be required to avoid interference with the guide rail See Installation Data Install remainder of the sump discharge piping This typically includes a vertical run of piping appropriately sized and configured to mate w...

Страница 4: ...ate Guide Rail Bracing Sump depths of 9 6 and greater require intermediate guide rail bracing The braces mount on the vertical discharge pipes with U bolts which are sized according to the discharge pipe size The number of guide rail braces required are as follows Sump Depths 9 6 to 18 0 1 guide rail brace required 18 6 to 27 0 2 guide rail braces required 27 6 to 30 0 3 guide rail braces required...

Страница 5: ... the pump or bottom of the basin Shorten cords to suit the installation See Bulletin Q 701 for the Installation and Service Manual on the electrical Control Panel system 11B Control Panel Mounted Remote from Basin If the Control Panel is remotely located instead of on the mounting stand at the basin install coupling through basin wall Screw protective bushing from inside basin into coupling all fu...

Страница 6: ...clogged Amperage higher than name plate will indicate this 2 Pump rotation may be wrong Reversing any two line leads on three phase pumps will reverse the rotation 3 Discharge plug valve may be closed 4 Plugging anywhere from impeller to sealing flange This is evident if no water runs out of sealing flange after raising the pump Pull the pump from the basin to find the clog 5 Plugging beyond the s...

Страница 7: ...LTRUDED RAIL I BEAM HYDRAULIC SEALING FLANGE ASSEMBLY WITH BUNA DIAPHRAGM right hand to suspend the float the pump should continue to run The pump should stop when raising the left hand to suspend the float If this procedure does not cause the pump to operate as described either order new 3900 mercury float switches or replace alternator relay PULTRUDED RAIL SYSTEM ...

Страница 8: ...XCEEDING 9 6 HYDROMATIC 3900 SUBMERSIBLE LEVEL SWITCHES HYDROMATIC NON CLOG SUBMERSIBLE PUMP HOPPER BOTTOM RECOMMENDED DISCH ELBOW FRP GUIDE RAIL LIFTING CHAIN VENT PIPING DEPTH OF WELL FT IN INFLUENT PIPE INV EL CONTROL POWER CABLES CONTROL CABLE MOUNTING BRACKET E G F SUMP SUMP SUMP MIN WATER LEVEL GRADE ELEV ELEV D C SIMPLEX 3 THROUGH 6 PUMPS ...

Страница 9: ... EXCEEDING 9 6 HYDROMATIC 3900 SUBMERSIBLE LEVEL SWITCHES HYDROMATIC NON CLOG SUBMERSIBLE PUMP HOPPER BOTTOM RECOMMENDED DISCH ELBOW FRP GUIDE RAIL LIFTING CHAIN VENT PIPING DEPTH OF WELL FT IN INFLUENT PIPE INV EL CONTROL POWER CABLES CONTROL CABLE MOUNTING BRACKET H F G E SUMP SUMP SUMP SUMP MIN WATER LEVEL GRADE ELEV ELEV DUPLEX 3 THROUGH 6 PUMPS ...

Страница 10: ...ons provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other than for what it is designed and man...

Страница 11: ......

Страница 12: ...___________________________ D Incoming line voltage _________________________ Actual _____________________________ E Voltage to pumps ____________________________ Actual _____________________________ F Type of junction box _____________________________ Manufacturer _______________________ G Are floats installed in wet well _______________________________________________________ H Are floats set to...

Отзывы: