Wiring

Connect input voltage (120 VAC, 60 HZ) to terminals 1 and 2.

  MODEL CG450

Connect terminal 2 to burner circuit neutral. Connect terminal P2 to 
burner Circuit in series with other limit controls. Consult boiler 
manufacturer instructions for proper terminal connections. Control 
should be wired in series with and before other limit controls.

Optional water feeder connection. Connect feeder N to terminal 2. 
Connect Feeder H to terminal 1. Connect feeder “FEED” or “W” to 
terminal A. For water feeders with 2 leads, connect feeder neutral 
to terminal 2 and feeder hot to terminal A. 

Note:

 

Use of a solenoid valve or McDonnell & Miller Model 101A 

water feeder may cause flooding and is not recommended for use 
with this low water cut-off.

Connect “BURNER” terminal on the CycleGard control to the orange 
burner wire (120VAC) located under the oil burner transformer.

See page 5 for schematic wiring diagram and additional 
SmartCycle description.

FACTORY

INSTALLED

JUMPER.

DO NOT

REMOVE

1

2

BURNER

POWER

SOURCE

120V

AC

+

0

LIMIT

CONTROLS

A

P2

P1

1

2

BURNER

WATER

FEEDER

3

4

OPTIONAL ACTIVATION

    

WARNING

   

Electrical shock hazard. 

To prevent electrical shock, death or equipment 

damage, disconnect power supply before installing or servicing control. 

  Install this control in accordance with all local codes and authorities having jurisdiction. Regulations 

of these authorities take precedence over the general instructions provided in this manual.

Содержание CycleGard CG450 Series

Страница 1: ...control cover 5 4 Low Water Cut Offs For Steam Boilers 120 VAC Operating Voltage Max Pressure 15 psi U S Patent Nos 5 739 504 6 390 027 CG450 Series CGT450 Series 126 Bailey Road North Haven CT 06473...

Страница 2: ...ting plate by slipping keyholes in back of chassis over pre mounted screws on plate Tighten screws B Using a wire nut attach a wire min 90 C to the pigtail lead in the control box Attach the other end...

Страница 3: ...cDonnell Miller Model 101A water feeder may cause flooding and is not recommended for use with this low water cut off Connect BURNER terminal on the CycleGard control to the orange burner wire 120VAC...

Страница 4: ...the ter minals on the tankless aquastat 4 Connect THERMOSTAT terminals on CycleGard control to T T terminals on burner primary control 5 6 Connect BURNER terminal on the CycleGard control to the oran...

Страница 5: ...ation The last four digits of the CycleGard model number determine the frequency and duration of the Intermittent Level Test ILT as shown in the table When the optional SmartCycle feature is activated...

Страница 6: ...Procedure above the boiler is foaming The CycleGard provides protection for foaming boilers see CycleGard Intermittent Level Test Feature on page 5 However to provide optimal steaming performance it...

Страница 7: ...odel No EL 1220 EL1214 P 3 4 NPT 2 SQUARE 17 8 313 16 15 16 1 3 4 NPT 5 16 2 SQUARE 17 8 49 16 1 3 4 NPT 5 16 111 16 EL1214 R REMOTE PROBE VXT Water Feeder The VXT Water Feeder available separately ca...

Страница 8: ...r implied including without limitation any warranty of MERCHANTABILITY or fitness for a particular purpose This warranty may not be assigned or transferred and any unauthorized transfer or assignment...

Отзывы: