8. Troubleshooting
8.1 Error code display on LED wire controller
Malfunction
Error code
Reason
Solution
Inlet water temperature
sensor failure
PP1
The sensor in open or short
circuit
Check or change the sensor
Outlet water temperature
sensor failure
PP2
The sensor in open or short
circuit
Check or change the sensor
Heating condenser
sensor failure
PP3
The sensor in open or short
circuit
Check or change the sensor
Gas return sensor failure
PP4
Connect some wire wrongly on
gas return sensor position
Confirm there is nothing on this
point, restart the machine
Ambient temperature
sensor failure
PP5
The sensor in open or short
circuit
Check or change the sensor
Temperature difference
between water inlet and
outlet is too much
PP6
Water flow volume not
enough ,water pressure
difference is too low
Check the water flow volume or
water jammed or not
Cooling outlet water
temperature is too low
PP7
Water flow volume is not
enough
Check the water flow or water
system is jammed or not
First grade antifreeze
protection in Winter
PP7
Ambient temperature or water
inlet temperature is too low
Water pump will run
automatically for first grade
antifreeze
Second grade antifreeze
protection in Winter
PP7
Ambient temperature or water
inlet temperature is too low
Heat pump will start heating for
second grade antifreeze
Cooling condenser
sensor failure
PP8
Connect some wire wrongly on
gas return sensor position
Confirm there is nothing on this
point, restart the machine
High pressure protection
EE1
1. Refrigerant is too much
2. Air flow is not enough
1. Discharge redundant
refrigerant from HP gas
system
2. Clean the air exchanger
Low pressure protection
EE2
1. Refrigerant is not enough
2. Water flow is not enough
3. Filter jammed or capillary
jammed
1. Check if there is any gas
leakage ,re-fill the
refrigerant
2. Clean the air exchanger
3. Replace the filter or
capillary
Flow switch closed
EE3 or "ON" Low water flow, wrong flow
direction, or flow switch failure.
Check if the water flow is
enough and flow in right
direction, or else the flow switch
could be failed.
Power supply
connections wrong (for 3
phase unit)
EE4
Wrong connection or lack of
connection
Check the connection of power
cable
Inlet and outlet water
temperature difference
malfunction
EE5
Water flow volume is not
enough ,water pressure
difference is too low
Check the water flow rate ,or
water system is jammed or not
Communication failure
EE8
Wire connection is not good
Check the wire connection
Содержание 7018522
Страница 12: ... 11 2 Dimension Hydro Pro 5 7 10 Hydro Pro 13 ...
Страница 15: ... 14 3 5 Typical arrangement Note This arrangement is only an illustrative example ...
Страница 21: ... 20 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 5 7 10 ...
Страница 22: ... 21 5 2 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 13 ...
Страница 23: ... 22 5 3 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 18 22 ...
Страница 24: ... 23 5 4 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 26 ...
Страница 30: ... 29 7 3 How to know the current status ...
Страница 34: ... 33 9 Exploded Diagram and Maintenance 9 1 Exploded Diagram Model 7 kw ...
Страница 43: ... 42 2 Dimension Hydro Pro 5 7 10 Hydro Pro 13 ...
Страница 52: ... 51 5 Câblage Electrique 5 1 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Hydro Pro 5 7 10 ...
Страница 53: ... 52 5 2 SCHEMA DE CABLAGE DE POMPE À CHALEUR DE PISCINE Hydro Pro 13 ...
Страница 54: ... 53 5 3 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Hydro Pro 18 22 ...
Страница 55: ... 54 5 4 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Hydro Pro 26 ...
Страница 61: ... 60 7 3 Comment savoir les états actuels ...
Страница 65: ... 64 9 Schéma eclaté et entretien 9 1 Schéma eclaté Modèle 7 kw ...
Страница 74: ... 73 2 Afmeting Dimension Hydro Pro 5 7 10 Hydro Pro 13 ...
Страница 83: ... 82 5 Elektrische bedrading 5 1 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 5 7 10 ...
Страница 84: ... 83 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 13 ...
Страница 85: ... 84 5 3 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 18 22 ...
Страница 86: ... 85 5 4 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 26 ...
Страница 92: ... 91 7 3 Hoe de huidige status te weten te komen ...
Страница 105: ... 104 2 Ausmaße Hydro Pro 5 7 10 Hydro Pro 13 ...
Страница 114: ... 113 5 Elektrische Verkabelung 5 1 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 5 7 10 ...
Страница 115: ... 114 5 2 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 13 ...
Страница 116: ... 115 5 3 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 18 22 ...
Страница 117: ... 116 5 4 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 26 ...
Страница 123: ... 122 7 3 Den aktuellen Status abrufen ...
Страница 145: ... 144 5 Электропроводка 5 1 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 5 7 10 ...
Страница 146: ... 145 5 2 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 13 ...
Страница 147: ... 146 5 3 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 18 22 ...
Страница 148: ... 147 5 4 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 26 ...
Страница 154: ... 153 7 3 Как узнать текущий статус ...
Страница 175: ... 174 5 Kable elektryczne 5 1 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 5 7 10 ...
Страница 176: ... 175 5 2 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 13 ...
Страница 177: ... 176 5 3 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 18 22 ...
Страница 178: ... 177 5 4 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 26 ...
Страница 183: ... 182 Należy zwrócić uwagę że ...